6 Operation
6.5
Basic status
Following "power on" and initialization, if applicable with a configured start-up delay, the device reaches
the basic status.
Default setting:
1
Display 1 - analog input
Timer runtime/timer remaining running time
If the timer is on and the function "Change display upon timer start" has been configured, display 2 shows
the previously finished timer runtime or the remaining running time.
6.6
User level
Any of up to 8 parameters can be selected via the setup program. In the default setting, the first setpoint
value and the switching differential are preset and can be changed using the buttons on the device.
Changing the setpoint value in the user level:
1. Press OK/Menu button twice.
Display 1 shows "1st SETPOINT VALUE",
Display 2 shows the currently parametrized setpoint value.
2. Press OK/Menu button once.
The setpoint value flashes.
3. Adjust the desired setpoint value by pressing the "Up"/"Down" button.
4. Press OK/Menu button once.
The setpoint value is set.
Changing the switching differential in the user level:
1. Press OK/Menu button twice.
Display 1 shows "1st SETPOINT VALUE",
Display 2 shows the currently parametrized setpoint value.
2. Press the "Down" button once.
3. Press OK/Menu button once.
Display 1 shows "SWITCHING DIFFERENTIAL",
Display 2 shows the currently parametrized switching differential.
The numeric value of the switching differential flashes.
4. Set the desired switching differential by pressing the "Up"/"Down" button.
Press OK/Menu button once.
The switching differential is set.
36
(1)
(2)
2
Display 2 - 1st setpoint value