Monthly Maintenance Schedule; Procedure For Inspecting The Air Inlet Filter; Replacing Or Updating The Boiler Control - FULTON Endura EDR Installation, Operation And Maintenance Manual

Condensing hydronic boilers 750,000 - 2,000,000 btu/hr featuring pure control
Table of Contents

Advertisement

MAINTENANCE
!
WARNING
Personnel performing burner
assembly maintenance must wear
appropriate respiratory protection.
Failure to do so may result in the
inhalation of refractory ceramic
bers.
4
CAUTION
All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes and
regulations.
All maintenance procedures should
be completed by trained personnel.
Appropriate training and instructions
are available from the Fulton Service
Department at (315) 298-5121 or
your local Fulton Heating Solutions
Representative.
In order to meet warranty conditions,
ensure all appropriate maintenance
activities are performed.
Burner gaskets must not be reused.
Gasket is designed for one-time use
only.
Using nuts and washers not provided
by Fulton can lead to ue gas leakage
and cause damage to the studs.
Follow proper safety precautions when
using a ladder.
4-4

Monthly Maintenance Schedule

Monthly maintenance must include the following:
1. Test high-limit control by reducing setting below the operating temperature;
burner should shut o . After readjusting the setpoint, reset the control.
2. Test operating temperature control by reducing temperature setting as
necessary to check burner operation.
3. Check ue gas temperature at outlet. If there is a temperature increase over
previous readings, the probable cause is soot or water-scale build-up on the
tubes. Consult Fulton Heating Solutions immediately if there is a concern.
4. Test low gas pressure switch and high gas pressure switch utilizing the
procedure in Operation section of this manual.
5. Inspect the combustion air inlet lter. If dust, lint or debris has accumulated,
replace the lter.

Procedure for Inspecting the Air Inlet Filter

Proceed as follows:
1. Remove the lter. The lter sits in the slot above the cabinet.
2. If debris has plugged or contaminated the lter, the lter must be replaced.
NOTE:
Operating the burner with the combustion air lter removed will void the
burner warranty. A clean lter of the same Fulton part number (type, size and
style) must be installed while the boiler is in operation.
3. Return the lter to its original position in the slot.

Replacing or Updating the Boiler Control

Only update the software or rmware when directed by the factory. Lead/Lag
integration requires the same rmware and software version on all units.
It is recommended to always update to the latest software when commissioning
new boilers.
SECTION 4
EDR-PURE-IOM-230608
© Fulton Group N.A., Inc. 2023