HYDRONIC PURE CONTROL™ USER MANUAL Endura (EDR) Endura+ (EDR+) Condensing Hydronic Boilers Condensing Hydronic Boilers 750,000 - 2,000,000 BTU/HR 2,500,000 - 6,000,000 BTU/HR Serial/ National Board Number Model Fulton Order Owner Site Name Date Hydronic-PURE-Control-UserManual-211214...
TABLE OF CONTENTS Hydronic-PURE-Control-UserManual-211214 UNIVERSAL DATA CONFIGURATION ..................3-49 Introduction LOCAL BOILER NETWORK STATUS ....................3-50 Overview ......................1-2 BMS NETWORK STATUS ......................3-51 Warnings & Cautions .................... 1-2 SYSTEM DIAGNOSTICS MENU ....................3-52 Disclaimers and Local Codes ................1-2 CONTROLS DIAGNOSTICS ......................3-52 CALL FOR HEAT DIAGNOSTICS ....................3-53 Installation SENSOR DIAGNOSTICS .......................3-53 LEAD/LAG DIAGNOSTICS ......................3-54...
INTRODUCTION INTRODUCTION HARDWARE AND NAVIGATION CONTROL MENUS DOWNLOADING A PROGRAM UPDATE PREPARING FOR LEAD/LAG OPERATION EXPORTING DATA USING THE FILE MANAGER BMS INTEGRATION Questions? Please Contact Your Local Manufacturer’s Representative...
The boiler heat exchanger is manufactured and stamped manual. in accordance with ASME Boiler and Pressure Vessel Code, Section IV for a maximum allowable working pressure Fulton reserves the right to change any part of this and operating temperature of 160 psig and 210°F (99°C), addendum. respectively.
Page 7
HARDWARE AND NAVIGATION INTRODUCTION HARDWARE AND NAVIGATION CONTROL MENUS DOWNLOADING A PROGRAM UPDATE PREPARING FOR LEAD/LAG OPERATION EXPORTING DATA USING THE FILE MANAGER BMS INTEGRATION Questions? Please Contact Your Local Manufacturer’s Representative...
EDR+ control display hardware is shown below and described in Table 1. Fulton reserves the right to change any part of this addendum and the corresponding Installation and Operation manual without notice.
Page 9
For detailed information specific to your boiler, please have your boiler FHS Serial Number and PURE Control™ software version ready and contact your Fulton Representative for further support. Questions? Please Contact Your Local Manufacturer’s Representative...
Page 10
This addendum should not be considered as a complete guide, nor should it replace existing guides or standards which may be applicable. Fulton reserves the right to change any part of this addendum and the corresponding Installation and Operation manual without notice.
Page 11
HARDWARE AND NAVIGATION SECTION 2 Hydronic-PURE-Control-UserManual-211214 Graphical Icon Reference Menu WARNING A listing and functional description of each of the graphical icons found within All information in this addendum is for reference and guidance purposes, the touchscreen menus is provided below in Table 2. and does not substitute for required professional training, conduct, and strict TABLE 2 - GRAPHICAL ICON REFERENCE MENU...
CONTROL MENUS INTRODUCTION HARDWARE AND NAVIGATION CONTROL MENUS DOWNLOADING A PROGRAM UPDATE PREPARING FOR LEAD/LAG OPERATION EXPORTING DATA USING THE FILE MANAGER BMS INTEGRATION Questions? Please Contact Your Local Manufacturer’s Representative...
Page 14
This addendum should not be considered as a complete guide, nor should it replace existing guides or standards which may be applicable. Fulton reserves the right to change any part of this addendum and the corresponding Installation and Operation manual without notice.
Page 15
CONTROL MENUS SECTION 3 Hydronic-PURE-Control-UserManual-211214 Boiler Status Screen WARNING Provides information on how the boiler is operating including VFD, LMV, and O2 Sensor readings and status. All information in this addendum is for reference and guidance purposes, and does not substitute for required professional training, conduct, and strict adherence to applicable jurisdictional/ professional codes or regulations.
Page 16
8 - L/L: Lag 5 *Boilers must be connected and 9 - L/L: Lag 6 configured for the Lead/Lag Factory Wired from Fulton Control- 10 - L/L: Lag 7 feature in order to be assigned a ler Port 1 11 - L/L: Lag 8 Lead/Lag position.
Page 17
Read Setpoint (SP) -50.0 – 250.0 Current Setpoint as determined Outdoor Air SP requires RTD or BMS 40024 by the Fulton Controller provided Temperature. INT16 - Outdoor Reset SP Read - Remote 4-20mA SP Field wiring for 0-10VDC - Remote 0-10VDC SP...
Page 18
3-Wire Shielded 40016 Board/sensor. Modbus INT16 Read Factory Wired D+/D-/SG Boiler Delta T -50.00 – 250.00 Calculated by the Fulton Control- 40019 ler. INT16 Utilizes Factory wired inlet/outlet Read RTD sensors Outdoor Air -50.00 – 250.00 Optional RTD sensor for Outdoor 40025 Air Temperature.
Page 19
CONTROL MENUS SECTION 3 Hydronic-PURE-Control-UserManual-211214 Safety Device Status Screen WARNING This screen provides real time statuses of boiler safeties and interlocks as well as a low water test feature. All information in this addendum is for reference and guidance purposes, Devices will either have a green circle to the left indicating closed circuit or and does not substitute for required a red circle indicating the device is open.
Page 20
(HGP) and Electrical Panel should it replace existing guides or Switch (PS) for the 4-6MM standards which may be applicable. units. Fulton reserves the right to change any part of this addendum and the corresponding Installation and Operation manual without notice. Low Gas...
Page 21
CONTROL MENUS SECTION 3 Hydronic-PURE-Control-UserManual-211214 Operator Control WARNING This screen is used for multiple functions: Start/Stop Deviations, Anti-Cycle Timer, and Manual Burner Control. All information in this addendum is for reference and guidance purposes, The start and stop deviations instruct the burner when to enable and disable and does not substitute for required around the setpoint temperature.
Page 22
Combustion should it replace existing guides or Manual SP standards which may be applicable. Boiler Start Fulton reserves the right to change any part of this addendum and Boiler Stop the corresponding Installation and Boiler Enabled / Disabled When disabled the Fulton...
Page 23
Units Description Modbus Register Boiler Run Hours 0 - 999,999 Hours Total Boiler Run hours as determined by 40042 the Fulton Controller. UINT32 Read Boiler Cycles 0 - 999,999 Cycles Total Boiler Cycles as determined by the 40044 Fulton Controller.
Page 24
Hydronic-PURE-Control-UserManual-211214 Alarm History WARNING The Fulton Controller will provide a chronological list of the last 100 alarms. Selecting the alarm number and pressing View Alarm Info will provide This addendum is specific to the usage additional information, including the LMV3 Error Code and Error Diagnostic, of the Hydronic PURE Control™...
Page 25
CONTROL MENUS SECTION 3 Hydronic-PURE-Control-UserManual-211214 Maintenance Log WARNING The Maintenance Log allows site personnel or service companies to log activities and maintenance performed on the boiler. You can view or add new entries from All information in this addendum is this screen.
Page 26
This addendum should not be considered as a complete guide, nor should it replace existing guides or standards which may be applicable. Fulton reserves the right to change any part of this addendum and the corresponding Installation and Operation manual without notice.
Page 27
Current Valve Open Current Valve Position Field Wiring to 40051 State Close as determined by the TB4-C1, TB4-C2, INT16 Fulton Controller. and/or TB4-C3 Read 3-15 Questions? Please Contact Your Local Manufacturer’s Representative...
Page 28
This addendum should not be considered as a complete guide, nor should it replace existing guides or standards which may be applicable. Fulton reserves the right to change any part of this addendum and the corresponding Installation and Operation manual without notice.
Page 29
CONTROL MENUS SECTION 3 Hydronic-PURE-Control-UserManual-211214 Parameter Range Units Factory Description Wiring Modbus Name Default Register WARNING Automatic Auto- Allows for select- Field Wiring to TB4-C4, 40055 Control/ matic able Auto/Manual and TB4-C5 INT16 All information in this addendum is Manual control for pump Read for reference and guidance purposes,...
Page 30
Delta P requires a 4-20mA signal from a field wired differential pressure sensor available to the staff responsible for TB4-A5 and TB4-A6 (not provided by Fulton). equipment operation. This addendum should not be considered as a complete guide, nor should it replace existing guides or standards which may be applicable.
Page 31
C7, and TB4-C8 that the pump will run at while Secondary Pump 2 in Manual con- Field Wiring to TB4- trol at the Fulton C9, and TB4-C10 Controller. 0-10VDC Output based on PID and Delta T or Delta P 3-19...
Page 32
Parame- Range Units Factory Description Wiring Modbus Fulton reserves the right to change ter Name Default Register any part of this addendum and Pump Delta T Delta T Selection for Sys-...
Page 33
All information in this addendum is TB4-A5 and TB4-A6 for reference and guidance purposes, (not provided by and does not substitute for required Fulton) professional training, conduct, and strict Delta 0.0 – 1000.0 Pres- High 20mA scaling Delta P requires...
Page 34
Ethernet switch (ships loose in trim kit when ordered). standards which may be applicable. Fulton reserves the right to change To enable Lead/Lag functionality, use the Auxiliary Configuration screen any part of this addendum and under the Admin category.
Page 35
CONTROL MENUS SECTION 3 Hydronic-PURE-Control-UserManual-211214 WARNING All information in this addendum is for reference and guidance purposes, and does not substitute for required professional training, conduct, and strict adherence to applicable jurisdictional/ professional codes or regulations. Follow all proper lockout/tagout procedures for service.
Page 36
This addendum should not be considered as a complete guide, nor should it replace existing guides or standards which may be applicable. Fulton reserves the right to change any part of this addendum and the corresponding Installation and Operation manual without notice.
Page 37
System -50.00 – 250.00 Calculation done by Uses field wired 40028 professional codes or regulations. Delta T the Fulton Controller. System Supply NT16 and System Return Read Temperatures. Follow all proper lockout/tagout Network Not User selectable.
Page 38
This addendum should not be considered as a complete guide, nor should it replace existing guides or standards which may be applicable. Fulton reserves the right to change any part of this addendum and the corresponding Installation and Operation manual without notice.
Page 39
CONTROL MENUS SECTION 3 Hydronic-PURE-Control-UserManual-211214 Lead Start 0.0 – 20.0 How far below Ethernet Cable setpoint the System Connection be- WARNING Supply temperature is tween boilers for allowed to be before Lead/Lag providing a call for All information in this addendum is heat to the Lead for reference and guidance purposes, boiler.
Page 40
Time. As boilers stage off, the remaining boilers firing rates will increase slightly Fulton reserves the right to change in order to adequately maintain the remaining system load. This process will any part of this addendum and...
Page 41
Delta T Protection (EDR+ Boilers Only) WARNING This modifier is mandatory and cannot be turned off or configured at the Fulton Control. As the delta T limit is approached, a factory-designated PID is used to All information in this addendum is slow the firing rate in an attempt to not pass the delta T limit.
Page 42
WARNING This modifier is mandatory and cannot be turned off or configured at the Fulton Control. This modifier is only active when Polypropylene is selected for This addendum is specific to the usage the venting material on the Auxiliary screen under Admin. When this type of of the Hydronic PURE Control™...
Page 43
CONTROL MENUS SECTION 3 Hydronic-PURE-Control-UserManual-211214 Local PID WARNING The Local PID contains a user-friendly PID interface for influencing boiler operation. All information in this addendum is for reference and guidance purposes, and does not substitute for required professional training, conduct, and strict adherence to applicable jurisdictional/ professional codes or regulations.
Page 44
This addendum should not be considered as a complete guide, nor should it replace existing guides or standards which may be applicable. Fulton reserves the right to change any part of this addendum and the corresponding Installation and Operation manual without notice.
Page 45
CONTROL MENUS SECTION 3 Hydronic-PURE-Control-UserManual-211214 Cold Start WARNING Cold start is an optional modifier that becomes active immediately after the call for heat. It is time / temperature based and will hold the boiler at low fire until All information in this addendum is those conditions are met.
Page 46
This addendum should not be considered as a complete guide, nor should it replace existing guides or standards which may be applicable. Fulton reserves the right to change any part of this addendum and the corresponding Installation and Operation manual without notice.
Page 47
CONTROL MENUS SECTION 3 Hydronic-PURE-Control-UserManual-211214 Outlet Monitoring WARNING Useful in Lead/Lag setups and unbalanced and/or low-flow conditions, the Outlet monitoring will drive the boiler firing rate to low fire if the outlet temperature All information in this addendum is becomes excessive.
Page 48
This addendum should not be considered as a complete guide, nor should it replace existing guides or standards which may be applicable. Fulton reserves the right to change any part of this addendum and the corresponding Installation and Operation manual without notice.
Page 49
CONTROL MENUS SECTION 3 Hydronic-PURE-Control-UserManual-211214 Parame- Range Units Factory Description Wiring Modbus ter Name Default Register WARNING Setpoint Outdoor Reset Local Determines Field wiring 40055 Selection BMS Analog 4-20mA Manual where the set- may be INT16 All information in this addendum is BMS Analog 0-10VDC point is coming required...
Page 50
This addendum should not be considered as a complete guide, nor should it replace existing guides or standards which may be applicable. Fulton reserves the right to change any part of this addendum and the corresponding Installation and Operation manual without notice.
Page 51
Current -50.0 – 250.0 Current Setpoint Field wiring 40024 Setpoint as determined may be INT16 WARNING by the Fulton required Read Controller. depending on what source is All information in this addendum is selected. for reference and guidance purposes, Minimum 40.0 –...
Page 52
INT16 standards which may be applicable. Fulton Controller. depending on Read / what source is Write Fulton reserves the right to change selected. any part of this addendum and Minimum 40.0 – 185.0 80.0 Absolute minimum the corresponding Installation and...
Page 53
CONTROL MENUS SECTION 3 Hydronic-PURE-Control-UserManual-211214 Scheduling Menu WARNING The Scheduling system allows for the operator to configure when the normal All information in this addendum is (occupied) setpoint will be maintained. This applies to the outdoor reset when for reference and guidance purposes, enabled.
Page 54
Setback Setback Allows the user to Enable / Set- Enabled override the setback Fulton reserves the right to change back Disable schedule and maintain any part of this addendum and the normal setpoint the corresponding Installation and operation regardless of the time of day.
Page 55
Hydronic-PURE-Control-UserManual-211214 Trending Screen WARNING Allows users to view current and past trending data when available to the Fulton All information in this addendum is Controller. The Trending data is continuously recorded by the control and can for reference and guidance purposes, be enabled or disabled by the operator.
Page 56
This addendum should not be considered as a complete guide, nor should it replace existing guides or standards which may be applicable. Fulton reserves the right to change any part of this addendum and the corresponding Installation and Operation manual without notice.
Page 57
CONTROL MENUS SECTION 3 Hydronic-PURE-Control-UserManual-211214 System Configuration WARNING Allows the user to set system parameters as shown below and in the table that follows. All information in this addendum is for reference and guidance purposes, and does not substitute for required professional training, conduct, and strict adherence to applicable jurisdictional/ professional codes or regulations.
Page 58
This addendum should not be considered as a complete guide, nor should it replace existing guides or standards which may be applicable. Fulton reserves the right to change any part of this addendum and the corresponding Installation and Operation manual without notice.
Page 59
CONTROL MENUS SECTION 3 Hydronic-PURE-Control-UserManual-211214 Domestic Hot Water Configuration WARNING Accessible only when Domestic Water is selected on the Auxiliary Configuration page. Allows control of a DHW pump based on an RTD All information in this addendum is temperature input. for reference and guidance purposes, and does not substitute for required The DHW call for heat occurs them Domestic Start temperature is reached,...
Page 60
C11 (Dry standards which may be applicable. contact) depending on Fulton reserves the right to change the control mode and/or any part of this addendum and boiler operation. the corresponding Installation and...
Page 61
CONTROL MENUS SECTION 3 Hydronic-PURE-Control-UserManual-211214 Universal Data Configuration WARNING Used to configure which boilers have access to information on the Lead/Lag network, either Hardwire, BMS, or shared. All information in this addendum is for reference and guidance purposes, Determines where certain information is coming from. and does not substitute for required professional training, conduct, and strict Can be different for each boiler and must be set up individually.
Page 62
Local Boiler Network Status Fulton reserves the right to change any part of this addendum and Shows communication and status between boilers connected in the Lead/Lag the corresponding Installation and Operation manual without notice.
Page 63
CONTROL MENUS SECTION 3 Hydronic-PURE-Control-UserManual-211214 BMS Network Status WARNING Shows communication and status between the control and the BMS or other connected Modbus device. All information in this addendum is for reference and guidance purposes, BMS Enable Override provides a way to satisfy the BMS enable (Network or Dry and does not substitute for required Contact) without needing to send a signal.
Page 64
It allows the user to take a System Snapshot, which records important system or repair any component of this settings and current operating values for analysis by Fulton. Please see Section 6 equipment unless you are qualified of this manual for more information on taking a system snapshot and transferring and fully understand all requirements it to a USB flash drive through the File Manager.
Page 65
CONTROL MENUS SECTION 3 Hydronic-PURE-Control-UserManual-211214 Call For Heat Diagnostics WARNING Provides the source for the boiler’s call for heat and all conditions that must be met in order for the boiler to run. All information in this addendum is for reference and guidance purposes, and does not substitute for required professional training, conduct, and strict...
Page 66
This addendum should not be considered as a complete guide, nor should it replace existing guides or standards which may be applicable. Fulton reserves the right to change Lead/Lag Diagnostics any part of this addendum and the corresponding Installation and Shows current estimated BTU load requirement for the system and when it Operation manual without notice.
Page 67
DOWNLOADING A PROGRAM UPDATE INTRODUCTION HARDWARE AND NAVIGATION CONTROL MENUS DOWNLOADING A PROGRAM UPDATE PREPARING FOR LEAD/LAG OPERATION EXPORTING DATA USING THE FILE MANAGER BMS INTEGRATION Questions? Please Contact Your Local Manufacturer’s Representative...
• Follow the gas supplier’s instructions. 2. Download the PURE Control™ software from the link provided by a Fulton • If you cannot reach your gas supplier, Heating Technician. Ensure that the file is downloaded. This may require the call the fire department.
Page 69
DOWNLOADING A PROGRAM UPDATE SECTION 4 Hydronic-PURE-Control-UserManual-211214 WARNING All information in this addendum is for reference and guidance purposes, and does not substitute for required professional training, conduct, and strict adherence to applicable jurisdictional/ professional codes or regulations. Follow all proper lockout/tagout procedures for service.
Page 70
This addendum should not be considered as a complete guide, nor should it replace existing guides or standards which may be applicable. Fulton reserves the right to change any part of this addendum and the corresponding Installation and Operation manual without notice.
Page 71
DOWNLOADING A PROGRAM UPDATE SECTION 4 Hydronic-PURE-Control-UserManual-211214 WARNING All information in this addendum is for reference and guidance purposes, and does not substitute for required professional training, conduct, and strict adherence to applicable jurisdictional/ professional codes or regulations. Follow all proper lockout/tagout procedures for service.
Page 72
Admin as the username, key in the password and considered as a complete guide, nor click OK. Contact Fulton technical support for the password, which will should it replace existing guides or be provided only to service technicians holding a valid Certificate of standards which may be applicable.
Page 73
USB port 1. If the issue persists, contact Fulton service and support line at (315) 298-5121. » If prompted with a message stating that the firmware is up to date, simply press OK and move on to installing the User App.
Page 74
Fulton reserves the right to change any part of this addendum and 10. In the middle of the screen, click on Import Application. A prompt asking the corresponding Installation and if you are sure you want to import the application will be displayed.
Page 75
DOWNLOADING A PROGRAM UPDATE SECTION 4 Hydronic-PURE-Control-UserManual-211214 WARNING All information in this addendum is for reference and guidance purposes, and does not substitute for required professional training, conduct, and strict adherence to applicable jurisdictional/ professional codes or regulations. Follow all proper lockout/tagout procedures for service.
Page 76
This addendum should not be considered as a complete guide, nor should it replace existing guides or standards which may be applicable. Fulton reserves the right to change any part of this addendum and the corresponding Installation and Operation manual without notice.
PREPARING FOR LEAD/LAG OPERATION INTRODUCTION HARDWARE AND NAVIGATION CONTROL MENUS DOWNLOADING A PROGRAM UPDATE PREPARING FOR LEAD/LAG OPERATION EXPORTING DATA USING THE FILE MANAGER BMS INTEGRATION Questions? Please Contact Your Local Manufacturer’s Representative...
The Ethernet switch can be purchased from Fulton and would be added to the equipment operation. trim kit. More information on Lead/Lag can be found in the Endura+ Installation and Operation Manual.
Page 79
PREPARING FOR LEAD/LAG OPERATION SECTION 5 Hydronic-PURE-Control-UserManual-211214 WARNING All information in this addendum is for reference and guidance purposes, and does not substitute for required professional training, conduct, and strict adherence to applicable jurisdictional/ professional codes or regulations. Follow all proper lockout/tagout procedures for service.
Page 80
This addendum should not be considered as a complete guide, nor should it replace existing guides or standards which may be applicable. Fulton reserves the right to change any part of this addendum and the corresponding Installation and Operation manual without notice.
Page 81
PREPARING FOR LEAD/LAG OPERATION SECTION 5 Hydronic-PURE-Control-UserManual-211214 9. Navigate to the Admin screen and select Universal Data Configuration. WARNING All information in this addendum is for reference and guidance purposes, and does not substitute for required professional training, conduct, and strict adherence to applicable jurisdictional/ professional codes or regulations.
Page 82
Fulton reserves the right to change 12. Verify that the Passive/Aggressive sliders on all boilers are as close to the any part of this addendum and same setting as possible.
EXPORTING DATA USING THE FILE MANAGER INTRODUCTION HARDWARE AND NAVIGATION CONTROL MENUS DOWNLOADING A PROGRAM UPDATE PREPARING FOR LEAD/LAG OPERATION EXPORTING DATA USING THE FILE MANAGER BMS INTEGRATION Questions? Please Contact Your Local Manufacturer’s Representative...
1. Navigate to the Admin screen by selecting Admin on the bottom left should it replace existing guides or navigation pane. standards which may be applicable. Fulton reserves the right to change 2. Click on System Diagnostics. any part of this addendum and the corresponding Installation and Operation manual without notice.
Page 85
EXPORTING DATA USING FILE MANAGER SECTION 6 Hydronic-PURE-Control-UserManual-211214 WARNING All information in this addendum is for reference and guidance purposes, and does not substitute for required professional training, conduct, and strict adherence to applicable jurisdictional/ professional codes or regulations. Follow all proper lockout/tagout procedures for service.
Page 86
PLC. should it replace existing guides or standards which may be applicable. Fulton reserves the right to change any part of this addendum and the corresponding Installation and Operation manual without notice.
Page 87
EXPORTING DATA USING FILE MANAGER SECTION 6 Hydronic-PURE-Control-UserManual-211214 Exporting Data Using File Manager WARNING Perform the following steps: All information in this addendum is for reference and guidance purposes, 1. Navigate to the Admin screen by selecting Admin on the bottom left and does not substitute for required navigation pane.
Page 88
This addendum should not be considered as a complete guide, nor should it replace existing guides or standards which may be applicable. Fulton reserves the right to change any part of this addendum and the corresponding Installation and Operation manual without notice.
Page 89
EXPORTING DATA USING FILE MANAGER SECTION 6 Hydronic-PURE-Control-UserManual-211214 WARNING All information in this addendum is for reference and guidance purposes, and does not substitute for required professional training, conduct, and strict adherence to applicable jurisdictional/ professional codes or regulations. Follow all proper lockout/tagout procedures for service.
Page 90
Fulton reserves the right to change 11. The files can now be transferred to a computer and distributed as needed. any part of this addendum and the corresponding Installation and Operation manual without notice.
BMS INTEGRATION INTRODUCTION HARDWARE AND NAVIGATION CONTROL MENUS DOWNLOADING A PROGRAM UPDATE PREPARING FOR LEAD/LAG OPERATION EXPORTING DATA USING THE FILE MANAGER BMS INTEGRATION Questions? Please Contact Your Local Manufacturer’s Representative...
2. Login using the Admin username and password. Fulton reserves the right to change any part of this addendum and 3. Select the Network tab from across the bottom of the screen. And then the corresponding Installation and ModBus from the available options.
Page 97
BMS INTEGRATION SECTION 7 Hydronic-PURE-Control-UserManual-211214 Modbus Scope Description Size Notes Units 40104 BMS Heartbeat INT16 An integer 1 must be written to this point con- tinuously Table Notes: 1. The decimal point is fixed to the tenths place, but not transmitted. For example, a value of 1000 equals 100.0 2.
Page 99
BMS INTEGRATION SECTION 7 Hydronic-PURE-Control-UserManual-211214 Information on “Alarm Info Screen” Alarm Index Alarm Name Alarm Screen Alarm Screen Solution Error Code Error Diagnostic Alarm Originator Alarm Notes Description Code Valve proving test No valve proving Valve proving activated, possible but pressure switch- min is selected as an input function for X9-04 (check parameter LMV...
Page 103
BMS INTEGRATION SECTION 7 Hydronic-PURE-Control-UserManual-211214 Information on “Alarm Info Screen” Alarm Index Alarm Name Alarm Screen Alarm Screen Solution Error Code Error Diagnostic Alarm Originator Alarm Notes Description Code Fuel / air control Curve points unde- Adjust the curve points fined for all actuators.
Page 105
BMS INTEGRATION SECTION 7 Hydronic-PURE-Control-UserManual-211214 Information on “Alarm Info Screen” Alarm Index Alarm Name Alarm Screen Alarm Screen Solution Error Code Error Diagnostic Alarm Originator Alarm Notes Description Code Error during stan- pneumatic operation Standardization was dardization started with pneumatic operation, standardiza- tion with pneumatic operation not possible.
Page 107
BMS INTEGRATION SECTION 7 Hydronic-PURE-Control-UserManual-211214 Information on “Alarm Info Screen” Alarm Index Alarm Name Alarm Screen Alarm Screen Solution Error Code Error Diagnostic Alarm Originator Alarm Notes Description Code Internal error Please contact your contact representative for information regarding this alarm, be sure to provide the LMV alarm code and diag- nostic code.
Page 109
BMS INTEGRATION SECTION 7 Hydronic-PURE-Control-UserManual-211214 Information on “Alarm Info Screen” Alarm Index Alarm Name Alarm Screen Alarm Screen Solution Error Code Error Diagnostic Alarm Originator Alarm Notes Description Code Trim function Upper limit trim func- Warning: trim function Error tion. is too long in limiting (ParNo 535;...
Page 111
BMS INTEGRATION SECTION 7 Hydronic-PURE-Control-UserManual-211214 Information on “Alarm Info Screen” Alarm Index Alarm Name Alarm Screen Alarm Screen Solution Error Code Error Diagnostic Alarm Originator Alarm Notes Description Code Program stop Program stop Program stop is active (no error) Alarm Outside Please contact your 1000 LMV or PLC...