FULTON Endura EDR Installation, Operation And Maintenance Manual page 54

Condensing hydronic boilers 750,000 - 2,000,000 btu/hr featuring pure control
Table of Contents

Advertisement

OPERATION
!
WARNING
All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes
and regulations. Failure to follow
instructions may result in a re or
explosion, causing property damage,
personal injury, or loss of life.
This boiler is equipped with an
ignition device, which automatically
lights the burner. Do not try to light
the burner by hand.
Do not store or use gasoline or
other ammable vapors and liquids
in the vicinity of this or any other
appliances.
Use only your hand to turn the valve
handle. Never use tools. If the knob
will not turn by hand, don't try to
repair it. Call a quali ed service
technician. FORCE OR ATTEMPTED
REPAIR MAY RESULT IN A FIRE OR
EXPLOSION.
WHAT TO DO IF YOU SMELL GAS • Do
not try to light any appliance. • Do
not touch any electrical switch; do
not use any phone in your building.
• Immediately call your gas supplier
from a neighbor's phone. Follow the
gas supplier's instructions. • If you
cannot reach your gas supplier, call
the re department.
A quali ed installer, service agency
or the gas supplier, must perform
installation and service.
Do not use this boiler if any part
has been under water. Immediately
call a quali ed service technician to
inspect the boiler and to replace any
impacted part of the control system.
3-2
Perform Pre-Start-Up Inspection
Prior to start-up, perform the following:
1. If you smell gas:
ƒ Do not try to light any appliance.
ƒ Do not touch any electrical switch; do not use any phone in your building.
ƒ Immediately call your gas supplier from a neighbor's phone.
2. Ensure the boiler is located with the proper clearances as shown in the
Clearances and Serviceability section of this manual.
3. Ensure that relief valves have been properly piped to oor drains.
4. Ensure ue gas from the boiler is properly vented.
5. Ensure the water system has been ushed and is free of debris.
6. Ensure combustion air openings are not obstructed in any way and have
adequate capacity.
7. Ensure there are no ammable liquids, materials or hazardous fumes
present in the environment.
8. Ensure nothing was damaged or knocked loose during installation and/or
shipment.
9. Inspect the main gas train and trim assembly to be sure they were not
damaged during shipment and/or installation.
Fill and Purge the System
Completely ll and purge the heating system as follows:
1. Close combination shuto /purge valve in supply, all drain cocks, the
shuto valve for the pressure reducing ( ll) valve, and all manual air vents.
2. Open a system valve, or ll through a drain connection.
3. Water will now begin to ll the system. Open the safety relief valve.
Continue lling until a constant stream of water (no bubbling) is
discharged from the safety relief valve.
4. At this point, the system has been initially lled. However, air pockets may
still remain at high points in the system and in heating loops above the
level of the safety relief valve valve. It is quite possible, depending on the
particular system that all piping above the safety relief valve still contains
air. If manual vents are installed on the system high points, these should
be opened to vent these locations. When only water is discharged from all
vents, the initial purging is complete.
5. With the gas shuto valve closed, turn on power to the boiler and operate
the circulator. Circulate the system water for approximately 30 minutes to
move all air to the automatic air separation point.
6. Check temperature/pressure indicator reading, which should equal the
pressure-reducing ( ll) valve set pressure. No more water should be
entering the system. Close the shuto valve on the cold-water ll line.
SECTION 3
EDR-PURE-IOM-230608
© Fulton Group N.A., Inc. 2023

Advertisement

Table of Contents
loading

Table of Contents