SECTION 2
EDR-PURE-IOM-230608
Install pH Neutralization Kit
The pH Neutralization Kit is a Fulton-provided kit designed to
bring the pH level of the boiler's condensate to a more neutral
level. It is not a replacement or alternative for the Condensate
Drain Trap. See Figures 17 and 18.
Adhere to the following for pH Kit installation:
1. Use CPVC, stainless, or galvanized pipe and ttings to
connect condensate trap to kit.
MULTIPLE BOILER
ASSEMBLY
B
F
(A) pH Kit Outlet
(B) Condensate Drain Trap
(C) Drain Outlet
(D) pH Kit Inlet
(E) pH Neutralization Kit
(F) Drain Inlet
Neutralizing Media
FIGURE 18 FIELD CONNECTIONS FOR CONDENSATE DRAIN TO PH NEUTRALIZATION TANK
Questions? Please Contact Your Local Manufacturer's Representative
E
D
C
I SOMETRI C VI EW
FRONT VI EW
Multiple Boilers
2. Connect kit downstream of Condensate Drain Trap. See
Figure 18.
3. Pipe outlet to appropriate drain. It is acceptable to use
PVC or CPVC on the outlet to drain.
4. Check condensate pH periodically.
NOTE:
Replacement bags are available from your Fulton
local representative. The medium in the container will
neutralize the condensate up to 12,000,000 BTU/hr for
approximately 6 months. (Fulton Part No. 2-30-001580)
SINGLE BOILER
ASSEMBLY
F
A
1
"
1/2
4-57-000440
1
"
1/2
1
"
1/2
4-50-000008
1"
2-30-001580
INSTALLATION
E
D
C
B
I SOMETRI C VI EW
FRONT VI EW
Individual Boiler
1
"
1/2
4-57-005500
"
3/4
1
"
1/2
4-50-000008
"
3/4
2-30-001580
A
2-21