FULTON Endura EDR Installation, Operation And Maintenance Manual page 98

Condensing hydronic boilers 750,000 - 2,000,000 btu/hr featuring pure control
Table of Contents

Advertisement

SERVICE DOCUMENTS
CONTROLS:
Boiler setpoint source (i.e. BMS, OAT, 4-20mA, Local)
Is the boiler configured for internal lead/lag?
Motorized isolation valve wired and functional? (Note: Variable-Primary only)
Dedicated primary pump wired and functional? (Note: Primary-Secondary only)
Software update performed?*
Software version in use:
SAFETY CHECKS: Check all safeties below for proper operation and document the final settings.
DEVICE
Low Water Safety
Air Switch
Low Gas Pressure Switch
High Gas Pressure Switch
Blocked Exhaust Switch
COMBUSTION SETTINGS: Fuel Type is:
FIRING POSITION:
Fuel Position
Air Position
Air Position
Air Position
Air Position
Blower Position
Air Position
Air Position
Air Position
Blower Ampere
Incoming Voltage
Supply Gas Pressure (InWC)*
Manifold Gas Pressure (InWC)*
MV Downstream Gas (InWC )*
Fan Discharge Pressure (InWC)*
Analyzer O2%
CO2 %
CO ppm
NOx @ 3%
Room Ambient Temp. °F
Combustion Air Temp. °F
Stack Temperature °F
Stack Draft (InWC)*
Inlet Water Temp. °F
Outlet Water Temp. °F
Main Flame Signal
When complete, please keep this form with the boiler, store a record copy in a safe location, and return a copy to Fulton:
Fulton
ATTN: Service Coordinator
972 Centerville Road
Pulaski, New York 13142
5-6
SETTING
OPERATIONAL
Natural Gas
P0
P1
P2
LIGHT
)*
* Use only a Slack Tube
DEVICE
High Temperature Limit
Fuel Train Leak Test
Blower/Premix Leak Test
Propane
P3
P4
P5
®
Manometer or equivalent. The use of a digital manometer is not recommended.
Phone: (315) 298-5121 • Fax: (315) 298-6390
SECTION 5
EDR-PURE-IOM-230608
YES
YES
YES
NO
NO
YES
YES
NO
NO
YES
VERSION:
*Do not skip this step unless instructed by the factory.
SETTING
OPERATIONAL
P6
P7
P8
2023-0607-EDR-PURE-IO-FORM.PDF
© Fulton Group N.A., Inc. 2023
NO
N/A
N/A
N/A
N/A
NO
P9
100%