SECTION 3
EDR-PURE-IOM-230608
ƒ Parameter Backup
Questions? Please Contact Your Local Manufacturer's Representative
1. Press and hold "F" and "A" until Code is displayed.
a. Then enter unit national board number press enter
once complete.
2. "400: Set" will be displayed
a. Press the"-"arrow three times until "000: Int" is
displayed.
b. Press the Enter button to get into "100:Int" parameters.
3.
Backup procedure:
a. Press the "+" button and go to P-050 (050
will be ashing).
b. Press enter > bAC_uP is displayed.
c. Press enter > 0 is displayed.
d Press "+" button and 1 is ashing
e. Press enter, after about 5 seconds a 0 appears on the
display indicating the end of the backup process.
NOTE:
If an error occurs during the backup process,
a negative value is displayed. For troubleshooting,
go to error code 137 to view diagnostic code.
OPERATION
3-9