10. Mains configuration
10.1 Mains parameter settings
The mains configuration is used in stand-alone applications which contain a mains feeder.
The above shows that the active power of the mains import/export is measured on the analogue input 91 and the reactive power on
analogue input 93 (in this example).
It is voluntary to use the "Mains Q input" if the ASC is only doing kW control of the inverters or are running the inverters at a fixed PF.
COMMISSIONING GUIDELINES 4189341077D EN
Page 27 of 58