8. Breaker connections

8.1

PV breaker is present

If the application configuration includes a PV breaker, the following terminals must be wired:
Terminal Function
14
Open PV Breaker
15
Common for 14/16
16
17
Close PV Breaker
18
Common for 17/19
19
It is noted that the breaker configuration is set up in the "Application configuration". There are no parameter menus for this. Compact
breaker (MCCB) is not supported by the ASC.
These menus and inputs associate with each other.
Terminal
Function
26
Feedback for the PVB open position
27
Feedback for the PVB closed position
28
Common for 26 and 27
Breaker feedback can be checked in the utility software on the inputs/outputs page. Note that the input terminal numbers are
mentioned on the right hand side of the terminal description.
COMMISSIONING GUIDELINES 4189341077D EN
Comments
NO
Open relay is used depending on breaker type: pulse
Comm
NC
NO
Closed relay is used depending on breaker type: pulse and continuous (contactor)
Comm
NC
Comments
2160 PVB open failure
2180 PVB pos failure
2170 PVB close failure
2180 PVB pos failure
Page 18 of 58