2.1.3 GOV/AVR analogue controller offset ..................................2.1.4 Using an analogue output as a transducer ................................. 2.2 PWM duty cycle ............................................2.2.1 Duty cycle .............................................. 2.2.2 Principle of duty cycles ....................................... Options E F AGC-4 Mk II 4189341277C EN Page 2 of 10...
2 x 0(4)-20 mA outputs Software version This document is based on the AGC-4 Mk II software version 6.00.0. Parameters The relevant parameters are 2781, 2783, and 5690 to 5991. For more information, see the Parameter list. Option F1 Option F1 is a hardware option: A PCB installed in slot #6, in addition to the standard hardware.
Legal information and disclaimer DEIF takes no responsibility for installation or operation of the generator set. If there is any doubt about how to install or operate the engine/generator controlled by the Multi-line 2 unit, the company responsible for the installation or the operation of the set must be contacted.
DEIF A/S reserves the right to change any of the contents of this document without prior notice. The English version of this document always contains the most recent and up-to-date information about the product. DEIF does not take responsibility for the accuracy of translations, and translations might not be updated at the same time as the English document.
NOTE The choice of resistor depends on the governor. Place the resistor at the governor/AVR end to avoid the signal being disturbed by noise. For more information, see Interfacing DEIF Equipment with Governors and AVRs and General Guidelines for Commissioning.
GOV/AVR can be inverted by selecting Inverse proportional in parameters 2781/2783. The following drawing is for option EF6, with the output limits set to ±25 mA. Options E F AGC-4 Mk II 4189341277C EN Page 7 of 10...
Genset apparent power 5860 Q Genset reactive power 5870 cos phi cos phi of the power from the genset 5880 f Genset frequency 5890 U Genset L1-L2 voltage Options E F AGC-4 Mk II 4189341277C EN Page 8 of 10...
The low level of the signal is between 0 and 0.5 volts, and the high level is between 5.7 and 6 volts. Voltage 5.7...6 V 0 0.5 V Time 0 100 % duty cycle Options E F AGC-4 Mk II 4189341277C EN Page 9 of 10...
When used as transducer outputs, the signal can be connected directly to 4-20 mA instruments as shown below. Transducer output 4-20 mA instrument or similar NOTE It is recommended to use instruments from the DQ series of DEIF instruments. Please refer to www.deif.com more information. Options E F AGC-4 Mk II 4189341277C EN...