COMMISSIONING GUIDE
Automatic Sustainable Controller,
DEIF A/S · Frisenborgvej 33 · DK-7800 Skive
Tel.: +45 9614 9614 · Fax: +45 9614 9615
info@deif.com · www.deif.com
ASC
Document no.: 4189341077A
SW version: 4.55.x or later

Advertisement

Table of Contents
loading

Summary of Contents for Deif ASC Series

  • Page 1 COMMISSIONING GUIDE Automatic Sustainable Controller, DEIF A/S · Frisenborgvej 33 · DK-7800 Skive Document no.: 4189341077A Tel.: +45 9614 9614 · Fax: +45 9614 9615 SW version: 4.55.x or later info@deif.com · www.deif.com...
  • Page 2: Table Of Contents

    Modbus master ..........................17 Modbus protocol and write type ...................... 17 Verification of the communication ....................17 Alarms for unicast communication ....................18 4. Measurements ..........................22 Voltage measurements ........................22 Nominal ratings ..........................23 DEIF A/S Page 2 of 26...
  • Page 3 ASC commissioning guide 4189341077 UK Emergency stop ..........................23 Application configuration, stand-alone .................... 24 Application configuration, power management ................25 Appendix, modified parameters list ..................... 26 DEIF A/S Page 3 of 26...
  • Page 4: General Information

    Legal information and disclaimer DEIF takes no responsibility for installation or operation of the generator set. If there is any doubt about how to install or operate the engine/generator controlled by the Multi-line 2 unit, the company responsible for the installation or the operation of the set must be contacted.
  • Page 5: About The Commissioning Guide

    Contents and overall structure This document is divided into chapters, and in order to make the structure simple and easy to use, each chapter will begin from the top of a new page. DEIF A/S Page 5 of 26...
  • Page 6: Introduction

    There are a few steps to follow when the ASC is configured. During the planning of the commissioning job, it can be useful to check whether the ASC is installed in the DEIF cabinet or in a customer-designed cabinet. This document can be used in both cases.
  • Page 7: Wiring Overview

    6 kW is presented as 6.0 in the lower scale (10-2500 V AC) and 6 kW in the second level scale (100-25000 V AC). So for low power installations, it is recommended to use 10 -2500 V AC. DEIF A/S Page 7...
  • Page 8: Power Supply

    Associated menus Feedback for the PVB open 2160 PVB open failure position 2180 PVB pos failure Feedback for the PVB closed 2170 PVB close failure position 2180 PVB pos failure Common for 26 and 27 DEIF A/S Page 8 of 26...
  • Page 9: Mains Breaker Is Present

    No control of the mains breaker is present. But it is necessary to wire in position feedbacks so the ASC knows the status of the mains breaker. This is the case for none power management systems. (ASC is the only DEIF controller in the system). Terminal...
  • Page 10: Transducer Signals

    4380, DG reactive power 20 mA value summated reactive power 4380, DG reactive power 4 mA value Notice that the 4-20 mA inputs are multi-inputs, and they must be configured correctly in the DEIF Utility SW. DEIF A/S Page 10...
  • Page 11: Ma Values

    Testing procedure of the transducer signals It is essential to test the transducer signals into the DEIF controller. Please follow these steps to verify the good functionality. All 4-20 mA inputs may be used. In the example, the mains power transducer is used (multi-configurable input 102).
  • Page 12 MB open position 0 kW 12 mA Display view, translated (suggestion) Display view master language PV380.0 380.0 380.0V PV380.0 380.0 380.0V Mains kW Analog 102 PROTECTION SETUP PROTECTION SETUP PROT CTRL SYST PROT CTRL SYST DEIF A/S Page 12 of 26...
  • Page 13 352 kW 16 mA Display view, translated (suggestion) Display view master language PV380.0 380.0 380.0V PV380.0 380.0 380.0V Mains kW 352kW Analog 102 352mA PROTECTION SETUP PROTECTION SETUP PROT CTRL SYST PROT CTRL SYST DEIF A/S Page 13 of 26...
  • Page 14 -349 kW 8 mA Display view, translated (suggestion) Display view master language PV380.0 380.0 380.0V PV380.0 380.0 380.0V Mains kW -349kW Analog 102 -349mA PROTECTION SETUP PROTECTION SETUP PROT CTRL SYST PROT CTRL SYST DEIF A/S Page 14 of 26...
  • Page 15 ASC commissioning guide 4189341077 UK Translation In the translations page, the multi-inputs can be translated: Displayed translation: (#### signifies the live value) Parameter list translation: (note #### signifies menu number). DEIF A/S Page 15 of 26...
  • Page 16 Fill in the readings of the display/utility SW as the example above shows. This will give a good indication whether the configuration is correct. Display reading Multi-conf. input 102 Multi-conf. input 105 Multi-conf. input 108 Signal mA DEIF A/S Page 16 of 26...
  • Page 17: Modbus Master

    DEIF ASC comm. ID 19200 Menu 7511 19200 Menu 7511 19200 Menu 7511 Now switch to unicast and adjust the DEIF ASC to a proper ID: Inverter number Inverter Modbus ID Baud rate selected DEIF ASC comm. ID 19200 19200...
  • Page 18: Alarms For Unicast Communication

    (ASCinverter). • 7570, PV comm error • 7580, PV Warning • 7590, PV Shutdown • 7520, Ext comm error Enable the alarms and configure the appropriate actions. DEIF A/S Page 18 of 26...
  • Page 19 When setting up the communication use the routing table set up the IP address you intend the HD67510 to have set up the Modbus slave details (communication to DEIF ASC) don’t disconnect the socket enable broadcast with ID 0 DEIF A/S...
  • Page 20 For remote monitoring (ASC reads from inverters), set up the translate table with your connected inverters, for example in this case, there are two inverters where the ASC reads from ID10 and ID11. All connected inverters must be included in the table for remote monitoring. DEIF A/S Page 20 of 26...
  • Page 21 Notice the dip switch position of the ADFweb. Both dip 1 and dip 2 have to be checked according to the manual from ADFweb. If one them is wrong, you cannot programme the device. DEIF A/S Page 21 of 26...
  • Page 22: Measurements

    415 volt system. Terminal Function Associated menus 6053, U nominal PV BUS 6051, U PT primary 6052, U PT secondary Notice that the terminal for the neutral is placed between L2 and L3. DEIF A/S Page 22 of 26...
  • Page 23: Nominal Ratings

    3491 Timer If used as e-stop then select 0 sec. 3492 Relay output for PLC 3493 Relay output for PLC 3494 Enable this alarms 3495 Select fail class If used as e-stop, then select S/D. DEIF A/S Page 23 of 26...
  • Page 24: Application Configuration, Stand-Alone

    Then the configuration is done by selecting the plant specifics. This example shows the plant with one ASC in a configuration with grid. The number of generators in the application cannot be configured on this screen unless it is a power management application. DEIF A/S Page 24 of 26...
  • Page 25: Application Configuration, Power Management

    ASC commissioning guide 4189341077 UK Application configuration, power management The power management provides a lot of combinations. The below screendump shows only an example. DEIF A/S Page 25 of 26...
  • Page 26: Appendix, Modified Parameters List

    As it may be noted, about ~35 parameters need to be changed in order to get a functioning system. This list is an example of a stand-alone system comprising a specific inverter. DEIF A/S Page 26 of 26...