Power source data

The power source data must be available before the commissioning starts.
For the example the plant consists of one mains incomer, three generators and nine inverters.
Table 2.3
Example of power source data for plant
Power source
Frequency [Hz]
generator 1
50
generator 2
50
generator 3
50
mains
50
solar panel
solar park
inverter size
inverter total
50
COMMISSIONING GUIDELINES 4189341077D EN
IP address
-
-
Function
ASC device IP number
Voltage [V]
400
400
400
400
400
Modbus ID, monitoring
3
4
Associated menus
9000
(9002 = IP/Subnet mask)
(9003 = Gateway)
Current [A]
S [VA]
PF
625
0.8
625
0.8
480
0.8
600
60
779
540
Modbus ID, control
P [kW]
CT ratio
PT ratio
500
1000/5
1:1
500
1000/5
1:1
384
1000/5
1:1
480
1000/5
1:1
0.265
557
1000/5
1:1
Baud rate
19200
19200
Amount
2100
9