Deif ASC-4 Commissioning Manuallines page 45

Automatic sustainable controller
Table of Contents

Advertisement

4. Set up the translate table:
a. Set up slave ID 0 for broadcast using UDP Broadcast and route it to the IP of the inverter.
Note that the desired slave ID address of the inverter has to be checked in the user manual of the inverter – 126 is for
example for SMA STP25000 TL.
b. Repeat steps for the number of IP addresses you have in your system (the example below shows a system with two (2)
inverters).
c. For remote monitoring (ASC reads from inverters), set up the translate table with your connected inverters, for example in
this case, there are two inverters where the ASC reads from ID10 and ID11.
d. All connected inverters must be included in the table for remote monitoring.
COMMISSIONING GUIDELINES 4189341077D EN
Page 45 of 58