Options 1, Zone Function - Bosch DS7240-UK Reference Manual

Control/communicator
Table of Contents

Advertisement

Pulse Count/Pulse Count Time Example:
Suppose you must program a zone function to detect four 60 ms pulses within 10 seconds before it declares the zone off-
normal. Follow these steps:
1.
Enter "4" in the Pulse Count address of the Zone Function you are configuring. "4" identifies the number of pulses the
panel must see.
2.
Since your time span is 10 seconds, this Zone Function will use a point scan time of 60 ms and is only for on-board zones
(see left side of Table 24). The selection for 10 seconds is 6. Enter "6" into the Pulse Count Time address of the Zone
Function you are configuring.
36.4

Options 1, Zone Function ##

• Address: See Table 22
• Default: See Table 22
• Selections: 0-15
Options 1, Zone Function
No Options Enabled
Enable Alarm Event Abort
Voice Verification
Armed for Perimeter Only Mode
Sensor Trouble Monitor
36.4.1
Parameter Description
Use the above options table when configuring the following zone function types:
• Chime Mode Only (0)
• 24-hr, Fire (1)
• 24-hr Fire with Alarm Verification (2)
• 24-hr Emergency (5), 24-hr Visible Panic (6)
• 24-hr Invisible Panic (7)
• 24-hr Burglary (8)
• Entry/Exit Delay 1(11)
• Entry/Exit Delay 2 (12)
• Follower (13)
• Instant (14)
For 24-hr Control Input (3), see Section 35.2.1.1 24-hour Control Input Zone Function Types on page 90.
For 24-hr Tamper (4), see Section 35.2.1.2 24-hour Tamper Input on page 91.
For Controlled Keyswitch (10), see Section 35.2.1.3 Controlled Keyswitch Types on page 91.