D268/D269, D279 Independent Zone Control; Figure 34: External Power For Command Centers - Bosch radlonlcs D6412 Installation Manual

Control/communicator
Hide thumbs Also See for radlonlcs D6412:
Table of Contents

Advertisement

D6412/D4412
Arming Devices
Back of Command Center
11.3

D268/D269, D279 Independent Zone Control

You can program on-board points 2 to 8 so that the D268, D269 or D279 (or later versions) Independent Zone
Controls operate as independent point controls (arms and disarms the point).
See Point Index Configuration in the D6412/D4412 Program Entry Guide (P/N: 45351) for programming
information. See the installation literature that accompanies the D268, D269 and D279 (or later versions) for
wiring and operation instructions.
In order to use the D268, D269 or D279 (or later versions) Independent Zone Control, you must
program the panel's on-board points for 1 k Ω Ω End of Line resistors. Points 2 to 8 must all be
supervised with 1 k Ω Ω resistors, even if an Independent Zone Control is only used for one point. See
Global Point Configuration in the D6412/D4412 Program Entry Guide (P/N: 45351) for programming
IMPORTANT
instructions. Only use on-board points 2-8 with an Independent Zone Control. No EOL resistor is used
on the points connected to the IZC.
45349D
Red
Yellow
Green
Black

Figure 34: External Power for Command Centers

D6412/D4412 Installation Guide
Green
Yellow
Black
Red
+
-
External 12 VDC
Power Supply
Page 48
R
Y
G
B
D6412/D4412 PCB
© 2002 Radionics

Advertisement

Table of Contents
loading

This manual is also suitable for:

Radlonlcs d4412

Table of Contents