Bosch DS7240-UK Reference Manual page 44

Control/communicator
Table of Contents

Advertisement

25.12 Cancel Event Enabled
• Address: 0234
• Default: 0 (No Cancel Reports)
• Selections:
• 0 = No Cancel Reports
• 1 = Cancel Reports Enabled
25.12.1 Parameter Description
If the Cancel Event is enabled (enter Data Digit 1 at Address 0234), a 'Cancel Window' starts with the initiation of alarm
events. The Cancel Window is equal to Bell Time. If the user acknowledges the alarm inside the cancel window, a Cancel
Event is created. If reporting is enabled, a Cancel [38] or Fire Cancel [39] report is sent.
If the Abort feature is enabled, the Cancel report is sent if the user acknowledges the alarm after the Abort Window has
expired but before the Cancel Window expires. Section 37.8 Alarm Event Abort Window on page 105 for more information.
If a user acknowledges a non-fire alarm event by entering their passcode before the Alarm Event Abort Window expires:
1.
The alarm event is aborted. Alarm, Cancel* and Restoral reports associated with the alarm are not transmitted. The alarm
event becomes a local only event.
2.
The user hears a unique three long beep tone at the keypad.
3.
The text keypad indicates the aborted alarm on the display. The LED keypad indicates the aborted alarm with a slow flash
in Alarm Memory.
* A Cancel Window starts with the initiation of the alarm event and follows Bell Time. If the user acknowledges the alarm inside
the cancel window (bell time), a Cancel [38] or Fire Cancel [39] report is sent. If the Abort feature is enabled, the Cancel report
is sent if the user acknowledges the alarm after the Abort Window has expired but before Bell Time expires.
25.13 Date Format and Enable PIN Trouble
• Address: 0235
• Default: See table below
• Selections: 0-3
Date Format & Enable PIN Trouble Options
No Options (US Date Display - MM/DD/YY)
International Date Display (DD/MM/YY)
Enable Default PIN Trouble
Reserved
Reserved
25.13.1 Parameter Description
This parameter controls the display of the date on the keypad and logged on the printer.
This parameter can also enable the System Trouble event that is generated if the default values for the Installer PIN and
User PIN are left unchanged. See Section 31.5 Installer PIN on page 74 and Section 32.1 PIN, User # on page 76 for more
information.
If either the default Installer PIN or the default User 1 PIN is changed using remote programming, the panel must
be reset at the end of the remote programming session.
The default setting of 1 sets the Date Format to the International format (DD/MM/YY) and disables the system trouble
message if the Installer PIN and User PIN defaults are left unchanged.
Page 44 P/N: 4998122677Cr1
PART III: PANEL PROGRAMMING
0
• •
Copyright © 2003 Bosch Security Systems
Enter This Data Digit to Select Options
1
2
3
4
5
6
7
8
• •
• •
• • • •
9 10 11 12 13 14 15
DS7240-UK Reference Guide

Advertisement

Table of Contents
loading

Table of Contents