51.4
Keypad Issues
Problem
I entered the Move to Area
function ([#] + [5] + [0]) at my
keypad, but it will not let me
move to another area.
I have a tamper trouble on a
zone that I cannot clear by
entering the Installer PIN and
then pressing the [System Reset]
key.
51.5
Miscellaneous Issues
Problem
There are numbers in brackets
[###] throughout this manual.
•
My printer is printing
strange characters and I
cannot read it.
52.0 Data Bus Address Quick Reference
Option Bus Address
DS7240-UK Reference Guide
Cause
•
The User's Authority Level does not
permit use of the Move to Area function.
•
There are no zones assigned to a
particular Area.
The zone is bypassed.
Cause
These numbers [###] refer to the event
numbers described "Panel Events and
Reporting Formats" on page 151.
The settings for the DX4010 RS-232 Serial
Interface Module may cause unexpected
printer output.
0
Installer Keypad or local connection to DSRPS-INT'L
1-8
40, 41
50
51
52-55
60-63
101-107
150, 151
250
Table 37: Data Bus Address Quick Reference
Copyright © 2003 Bosch Security Systems
•
Program at least one zone and assign it to an
Area. The Move to Area function should work
as defined.
•
Set the user's Authority Level to permit use of
the Move to Area function (contact Bosch
Security Systems Technical Service for
assistance).
Press the [Bypass] key to manually unbypass the
zone. Then enter the Installer's PIN. Then press
the [System Reset] key.
See "Data Bus Device Configuration" on page 120.
Verify the settings for the following parameters:
•
"DX4010 Output Configuration" (Address 1253)
•
"Baud Rate Configuration" (Address 1254)
•
"Parity/Flow Control/Stop Bit Configuration"
(Address 1255).
Device Description
Keypads 1-8
DX8010 Telephone Control Module
Premises RF Receiver 1
Premises RF Receiver 2
Premises RF Keypads Receiver 1
Premises RF Keypads Receiver 2
DX2010 Wired Input Expanders
DX3010 Octo-Output Expanders
DX4010 Serial RS-232 Interface Module
Solution
Solution
N/A
P/N: 4998122677Cr1 Page 143