Details Of Flags - Omron CK3M Seres Hardware User Manual

Programmable multi-axis controller
Table of Contents

Advertisement

6-4-2

Details of Flags

 CK3WHWChange
Register name
Description
Range
Details
Detection timing
Recovery
Effects
Cause and cor-
rection
Precautions/
Remarks
CK3M/CK5M Series Programmable Multi-Axis Controller Hardware User's Manual (O036)
Sys.CK3WHWChange
The CK3W hardware configuration was changed during operation.
0 to 1
Checks if there were any changes in the configurations of the connected CK3W Unit
and End Cover during operation.
0: No changes in hardware configurations during operation
1: Changes in hardware configurations during operation
Continuous
Cycle the power supply, or issue reset command ($$$)
Operation continues
Cause (Assumed cause)
The CK3W Unit address
switch was changed during
operation.
The CK3W Unit or End
Cover was disconnected
during operation.
Contamination with conduc-
tive object
Noise
Data corruption in bus
signals
Malfunction of bus inter-
face circuit
The CPU Unit or the CK3W
Unit has failed
Internal bus contact fail-
ure
None
Correction
Check if there were any
changes in the address
switch.
Make sure that the Units
are installed correctly.
If there is conductive mate-
rial nearby, blow air through
the Unit.
If the error occurs even af-
ter making the above cor-
rection, check noise entry
paths such as the FG and
the power supply lines and
implement noise counter-
measures as required.
If this error persists even
after you make the above
two corrections, replace the
CPU Unit or the CK3W
Unit.
6 Troubleshooting
Prevention
None
None
Do not perform any metal
work in the vicinity of the
control panel.
Make sure that the work en-
vironment is free of dirt and
dust.
Then close the control pan-
el.
Implement noise counter-
measures.
None
6-11
6

Advertisement

Table of Contents
loading

Table of Contents