5 Wiring
5-5

Analog Input Unit Wiring

This section describes the wiring for the analog input connection terminal block.
5-5-1

Wiring the Terminals

Applicable Wires
The wires that you can connect to the terminal block are twisted wires, solid wires, and ferrules that
are attached to the twisted wires. The following section describes the dimensions and processing
methods for applicable wires.
 Using Ferrules
If you use ferrules, attach the twisted wires to them.
Observe the application instructions for your ferrules for the wire stripping length when attaching
ferrules.
Always use plated one-pin ferrules. Do not use unplated ferrules or two-pin ferrules.
The applicable ferrules, wires, and crimping tools are listed in the following table.
Manufactur-
er
Phoenix Con-
tact
Weidmüller
 Using Twisted or Solid Wires
Wire type
Solid wire
Twisted wire
Required Tools
Use a flat-blade screwdriver to remove wires.
The recommended screw driver is as follows.
Model
SZF 0-0,4X2,5 Phoenix Contact
5-40
Applicable wire
Ferrule model
2
(mm
AI0,5-10
0.5 (#20)
AI0,75-10
0.75 (#18)
AI1,0-10
1.0 (#18)
AI1,5-10
1.5 (#16)
H0.5/16
0.5 (#20)
H0.75/16
0.75 (#18)
H1.0/16
1.0 (#18)
H1.5/16
1.5 (#16)
Conductor cross-sectional area
2
0.14 to 1.5 mm
Manufacturer
CK3M/CK5M Series Programmable Multi-Axis Controller Hardware User's Manual (O036)
(applicable wire size given in parentheses)
(AWG))
Phoenix Contact
CRIMPFOX 6 (0.25 to 6 mm
Weidmüller
PZ6 Roto (0.14 to 6 mm
Conductor length
(stripping length)
10 mm
Crimping Tool
2
, AWG24 to 10)
2
, AWG26 to 10)

Advertisement

Table of Contents