Using Ferrules
If you use ferrules, attach the twisted wires to them.
Observe the application instructions for your ferrules for the wire stripping length when attaching fer-
rules.
Always use plated one-pin ferrules. Do not use unplated ferrules or two-pin ferrules.
The applicable ferrules, wires, and crimping tools are listed in the following table.
Manufacturer
Phoenix Con-
tact
Weidmüller
Using Twisted or Solid Wires
Wire type
Conductor cross-sectional area
Solid wire
0.2 to 4 mm
Twisted wire 0.2 to 2.5 mm
5-1-4
Grounding
The type of ground terminal on the Power Supply Unit is a functional ground terminal.
A functional ground terminal takes protective measures for device and system functions, including pre-
vention of noises from external sources, and prevention of noises from devices or equipment that may
have harmful effects on other devices or equipment.
• Ground to 100 Ω or less, and when possible use a separate ground from those of other devices.
• If using an independent ground is not possible, then use a common ground. Connect to the ground
pole of the other device.
• Never use a common ground particularly with a motor, inverter, or other type of high-power equip-
ment. Use an independent ground so that the devices do not affect each other.
• To reduce the risk of receiving an electric shock, do not connect devices to ground poles to which
multiple devices are connected.
• Use a ground pole as close to the Power Supply Unit as possible and keep the ground line as short
as possible.
CK3M/CK5M Series Programmable Multi-Axis Controller Hardware User's Manual (O036)
Applicable wire
Ferrule model
2
(mm
(AWG))
AI0,25-8
0.25 (#24)
AI0,5-8
0.5 (#20)
AI0,75-8
0.75 (#18)
AI1,0-8
1.0 (#18)
AI1,5-8
1.5 (#16)
H0.25/12
0.25 (#24)
H0.34/12
0.34 (#22)
H0.5/14
0.5 (#20)
H0.75/14
0.75 (#18)
H1.0/14
1.0 (#18)
H1.5/14
1.5 (#16)
2
2
Crimping Tool
(applicable wire size given in parentheses)
Phoenix Contact
CRIMPFOX 6 (0.25 to 6 mm
Weidmüller
PZ6 Roto (0.14 to 6 mm
Conductor length
(stripping length)
8 mm
8 mm
5 Wiring
2
, AWG24 to 10)
2
, AWG26 to 10)
5-3
5