4.4. Connect to Power and Ethernet

Before You Begin
CAUTION
Connecting power with reverse polarity or using the wrong type of power supply may damage the
equipment. Make sure that the power supply is connected correctly and of the recommended type.
IMPORTANT
Connecting the Bolt II to PoE and DC power simultaneously may result in a current loop that could
damage both the power sources and the Bolt II. Ensure to use only one of the power connections at
a time.
IMPORTANT
When Bolt II is powered via the power connector, Functional Earth (FE) must be connected.
Power Supply Requirements
• Use insulated power supply 10-33 VDC, minimum 2 W.
2
• Use 0.25 - 1.5 mm
(24-16 AWG) cable for supply wiring.
• Use minimum 90 °C copper (Cu) wire only.
Ethernet Cable Requirement
If the Ethernet cables are to be exposed in an outdoor environment, transient protection must be provided.
Functional Earth (FE) Wire Screw Placement
When Bolt II is mounted on a sheet metal plate, connect Functional Earth (FE) to the plate near Bolt II.