Installing Fire Dampers - Huawei FusionCol8000-E260 Quick Manual

Modular indirect evaporative cooling system
Hide thumbs Also See for FusionCol8000-E260:
Table of Contents

Advertisement

FusionCol8000-E260 Modular Indirect Evaporative
Cooling System
Quick Guide (FDC Scenario)
If both fire prevention and air stopping are needed, use fire dampers. After the
unit shuts down, the air dampers are closed to isolate the unit from the air ducts.
Procedure
Step 1 Install a fire damper at the indoor air discharge vent of the unit based on the site
requirements.
Step 2 Install a fire damper at the outdoor air exhaust vent of the unit based on the site
requirements.
Step 3 Connect cables to the fire dampers. Route the cables through the signal cable
holes at the bottom of the unit and connect them to the signal terminals.
Figure 8-1 Connecting cables to the supply air fire damper
Issue 01 (2022-06-30)
8
Copyright © Huawei Digital Power Technologies Co., Ltd.

Installing Fire Dampers

8 Installing Fire Dampers
40

Advertisement

Table of Contents
loading

Table of Contents