Quick Guide (FDC Scenario)
Procedure
Step 1 Commission the continuous cooling devices.
Table 11-1 Devices to be commissioned
Backup Power Device
SmartLi-512V-162Ah-F-03-A
FusionCol8000-EBC600
PDU8000-1250D9-BS310
Step 2 Turn on all output switches of the lithium battery cabinets or lead-acid power
control cabinets.
Step 3 Turn on all output switches in the combiner cabinet.
Step 4 Check that the positive and negative DC input power cables of all EHUs are
correctly connected.
Step 5 Measure the DC input voltage. The value should range from 721 V DC to 729 V
DC.
Figure 11-1 Measuring voltage
----End
Issue 01 (2022-06-30)
Copyright © Huawei Digital Power Technologies Co., Ltd.
11 Power-On Commissioning
Reference Document
SmartLi 3.0 User Manual (Short-Term
Backup Power)
FusionCol8000-EBC600 User Manual
PDU8000 DC Combiner Cabinet User
Manual