FusionCol8000-E260 Modular Indirect Evaporative
Cooling System
Quick Guide (FDC Scenario)
Categor
y
Compres
sor
Differen
tial
pressure
switch
Air filter
Table 10-2 Cable connection checklist
Check Item
Cables are intact and free from sharp bends.
No open or short circuit, or incorrect connection occurs in
electrical circuits.
All cables for the unit are properly connected as required.
The rated specifications of the upstream general switch
meet the maximum current requirement.
All cables, connectors, and screws are secured.
The device is properly grounded.
Table 10-3 Pipe checklist
Check Item
All pipes are secured.
All thermal insulation foam on pipes is intact.
Water pipe joints are sealed with sealing tape or sealant.
Issue 01 (2022-06-30)
Check Item
The water tank is free of foreign matter, and
the filter and drainage port are not blocked.
The water pan is free of foreign matter inside
and its drainage port is unblocked.
The sheet metal fasteners on the compressor
have been removed.
The bolts for securing the compressor are
tightened.
The pressure inlet tube is secured using cable
ties and not deformed.
The pressure inlet tube is not blocked or bent.
The protective film on the air filter has been
removed.
The air filter is correctly installed according to
the airflow direction marked on the frame.
Copyright © Huawei Digital Power Technologies Co., Ltd.
10 Verifying the Installation
Check Result
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
Check Result
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
Check Result
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
45