FusionCol8000-E260 Modular Indirect Evaporative
Cooling System
Quick Guide (FDC Scenario)
No.
2
3
4
5
6
7
8
The unit can be connected to a smoke sensor, remote startup/shutdown signal,
common alarm signal, and water sensor. The following describes how to connect a
water sensor.
Procedure
Step 1 Install the water sensor based on the actual scenario.
Step 2 Connect one end of the water sensor cable to the water sensor.
Step 3 Route the signal cable through the signal cable hole at the bottom of the electric
control box.
Step 4 Connect the signal cable to X502 terminals 1 and 2.
Issue 01 (2022-06-30)
X501
X502
Smoke
Water
sensor
sensor
Remote
Fresh intake
startup/
air damper
shutdown
24 V DC
Remote
Fresh intake
startup/
air damper
shutdown
GND
Common
Fresh intake
alarm 1+
air damper
U
(feedback)
Common
Fresh intake
alarm 1–
air damper
Y (control)
Common
Reserved
alarm 2+
Common
Reserved
alarm 2–
Copyright © Huawei Digital Power Technologies Co., Ltd.
X504
X505
Outdoor
Indoor
exhaust air
return air
damper GND
damper
GND
Outdoor
Indoor
exhaust air
return air
damper U
damper U
(feedback)
(feedback)
Outdoor
Indoor
exhaust air
return air
damper Y
damper Y
(control)
(control)
Indoor supply
Fresh air
air damper
exhaust
24 V DC
damper 24 V
DC
Indoor supply
Fresh air
air damper
exhaust
GND
damper
GND
Indoor supply
Fresh air
air damper U
exhaust
(feedback)
damper U
(feedback)
Indoor supply
Fresh air
air damper Y
exhaust
(control)
damper Y
(control)
7 Installing Cables
X510
Exhaust
bypass air
damper GND
Exhaust
bypass air
damper U
(feedback)
Exhaust
bypass air
damper Y
(control)
Reserved
Reserved
Reserved
Reserved
35