FusionCol8000-E260 Modular Indirect Evaporative
Cooling System
Quick Guide (FDC Scenario)
Tab
Issue 01 (2022-06-30)
Parameter
Fan backup-power
Compressor backup-
power
Require password to
start or shutdown
onsite
System power limit
Auxiliary cooling
power limit
Balance of water and
electricity
consumption
Altitude
Wet mode startup
temperature
Dehumidifying
function
Copyright © Huawei Digital Power Technologies Co., Ltd.
11 Power-On Commissioning
Description
● 0%: The unit does not have backup
power.
● 100%: The fan has backup power.
● 0%: The compressor does not have
backup power.
● 50%: The compressor has backup
power that is 50% of the
compressor system power.
● 100%: The compressor has backup
power that is 100% of the
compressor system power.
● No: No password is required for
startup or shutdown.
● Yes: A password is required for
startup and shutdown.
This parameter ensures that the total
operating power of the system is
always below the preset value.
This parameter ensures that the
operating power for auxiliary cooling is
always below the preset value.
This parameter can be set to Power
saving mode, Normal water saving
mode, Extreme water saving mode,
Customized mode, or Disable water
mode. Set this parameter based on the
site requirements.
NOTE
You are advised to retain the default value.
Set this parameter based on the actual
altitude.
This parameter is displayed when
Balance of water and electricity
consumption is set to Customized
mode.
Set this parameter as required.
● Enable: The device starts
dehumidifying when the ambient
humidity is higher than the
humidity setpoint.
● Disable: The dehumidifying function
is disabled.