Huawei FusionCol8000-E260 Quick Manual page 45

Modular indirect evaporative cooling system
Hide thumbs Also See for FusionCol8000-E260:
Table of Contents

Advertisement

FusionCol8000-E260 Modular Indirect Evaporative
Cooling System
Quick Guide (FDC Scenario)
● The default T/H sensor address is 1.
● After the addresses are set, power on the device, choose Settings > System
Settings > T/H sensor on the home screen of the display module, and set the
sensors in the aisles corresponding to the addresses to Enable. Otherwise, the
sensors will not work.
● If the T/H sensor provided uses an eight-bit DIP switch, bits 1 to 6 of the DIP
switch are used to set the device address, bit 7 is reserved, and bit 8 is used to
switch the temperature display mode.
----End