FusionCol8000-E260 Modular Indirect Evaporative
Cooling System
Quick Guide (FDC Scenario)
Figure 7-10 Connecting communications cables
----End
7.6.3 CAN Teamwork + FE Monitoring
Step 1 Connect teamwork and monitoring communications cables.
Networking
Protocol
Description
Figure 7-11 Connecting communications cables
----End
Issue 01 (2022-06-30)
CAN Teamwork
CAN
One teamwork network
supports a maximum of 32
units. On the Teamwork
Settings screen of the display
modules of the first and last
units, set Enable teamwork
CAN resistor to Yes.
NO TE
Customers can purchase a switch and NetEco as the monitoring system.
Copyright © Huawei Digital Power Technologies Co., Ltd.
7 Installing Cables
FE Monitoring
Modbus-TCP/SNMP
-