FusionCol8000-E260 Modular Indirect Evaporative
Cooling System
Quick Guide (FDC Scenario)
Tab
Issue 01 (2022-06-30)
Parameter
DO_1 action
DO_2 action
DO_1
Copyright © Huawei Digital Power Technologies Co., Ltd.
11 Power-On Commissioning
Description
This parameter can be set to On or
Off, and is used together with DO_1.
For details, see DO_1 description.
This parameter can be set to On or
Off, and is used together with DO_2.
For details, see DO_2 description.
● If this parameter is set to Smoke &
Water only, DO_1 acts according to
DO_1 action when a smoke or
water overflow alarm is generated.
● If this parameter is set to Critical
alarm, DO_1 acts according to
DO_1 action when a critical alarm
is generated.
● If this parameter is set to Major
alarm, DO_1 acts according to
DO_1 action when a major alarm is
generated.
● If this parameter is set to Alarm,
DO_1 acts according to DO_1
action when a critical alarm, major
alarm, or warning is generated.
● If this parameter is set to Startup
status, DO_1 acts according to
DO_1 action when the unit is
started.
● If this parameter is set to No, no
alarm is generated when DO_1 is
disconnected.
57