Quick Guide (FDC Scenario)
If the unit is not started and placed at a low temperature (≤ –20°C), the
maintenance door may frost and the door rubber strip may freeze. If so, do not
forcibly open the maintenance door.
When the unit is started, set the supply air temperature to 25°C, preheat the unit
for 30 minutes, and then open the maintenance door.
Table 10-1 System checklist
Categor
y
Unit
Fan
Water
system
Issue 01 (2022-06-30)
10
CA UTION
Check Item
The unit is installed properly without any tilt.
Foreign matter (such as desiccant, cable ties,
cable ends, dust, iron scraps, copper wires, and
aluminum scraps) inside the cabinet has been
removed.
The outdoor exhaust fan is secured after it is
turned over.
The fan interconnection terminals are
connected.
There is no foreign matter inside the fan.
The fan blades rotate properly.
The water pump is secured.
The water filter is secured.
The liquid level sensor runs smoothly.
Pipes are connected securely without leakage.
Copyright © Huawei Digital Power Technologies Co., Ltd.

Verifying the Installation

10 Verifying the Installation
Check Result
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed