Fe Teamwork + Rs485 Monitoring - Huawei FusionCol8000-E260 Quick Manual

Modular indirect evaporative cooling system
Hide thumbs Also See for FusionCol8000-E260:
Table of Contents

Advertisement

FusionCol8000-E260 Modular Indirect Evaporative
Cooling System
Quick Guide (FDC Scenario)

7.6.4 FE Teamwork + RS485 Monitoring

Step 1 Connect teamwork and monitoring communications cables.
Networking
Protocol
Note
Issue 01 (2022-06-30)
FE Teamwork
MAC_CAN
A teamwork network supports
a maximum of 16 units.
NO TE
● Connect the COM/FE port on the main control module of the last unit in each group to
the RS485 port on the host.
● Customers can purchase an ECC and NetEco as the monitoring system.
Copyright © Huawei Digital Power Technologies Co., Ltd.
7 Installing Cables
RS485 Monitoring
Modbus-RTU
n seconds to
It takes 3 x
n units. If
collect data from
the time required for the host
to collect data from all units
does not meet the
performance requirements,
group the units.
● If units are not grouped (
= 1), set RS485 monitoring
grouping to Enable on the
Modbus Settings screen
for each unit.
● If units are grouped (
n ≤ 4), set
recommended:
RS485 monitoring
grouping to Enable on the
Modbus Settings screen
for the unit with the
COM/FE port connected.
Retain the default setting
(Disable) for other units.
n
n > 1;
30

Advertisement

Table of Contents
loading

Table of Contents