FusionCol8000-E260 Modular Indirect Evaporative
Cooling System
Quick Guide (FDC Scenario)
Item
T/H sensor cable,
water sensor (rope
type), and
teamwork and
monitoring
communications
cables
Fire damper cable
Air damper cable
Equipotential
ground lug/ground
cable
Table 2-4 Cable terminal requirements (default power)
Connector
Power cable terminal
Power PE cable
terminal
Standby DC power
cable terminal
Table 2-5 Cable terminal requirements (maximum power)
Connector
Power cable terminal
Power PE cable
terminal
Issue 01 (2022-06-30)
Recommended Specifications
CAT 5e or higher shielded network cable
Power cable: 3 x 1 mm
Feedback signal cable: 2 x 22 AWG outdoor copper cable
4 x 1 mm
● Ground lug: Use hot-dip zinc-coated flat steel sheet
with a cross-sectional area greater than or equal to 50
mm
● Ground cable: Use equipotential ground cables with a
cross-sectional area of at least 16 mm
ground cables through a plastic-coated metal hose.
Copyright © Huawei Digital Power Technologies Co., Ltd.
2
outdoor copper cable
2
outdoor copper-core cable
2
.
Terminal Specifications
AC bare crimp terminal,
2
DT, 70 mm
, M20, tin
plating
Bare crimp terminal, DT,
2
35 mm
, M10, tin plating
AC bare crimp terminal,
2
DT, 50 mm
, M10, tin
plating
Terminal Specifications
AC bare crimp terminal,
2
DT, 95 mm
, M20, tin
plating
Bare crimp terminal, DT,
2
50 mm
, M10, tin plating
2 Materials
2
and route the
Quantity
6
2
2
Quantity
6
2
4