Annex A; Overload Characteristic; Overload Protection In The Lower Speed Range - KEB COMBIVERT F5 Series Instruction Manual

Hide thumbs Also See for COMBIVERT F5 Series:
Table of Contents

Advertisement

Annex

Annex A

A.1

Overload characteristic

Time [s]
300
270
240
210
180
150
120
90
60
30
0
105 110 115 120 125 130 135 140 145 150 160
The characteristic declines device-dependently in this range
(see unit identification).
On exceeding a load of 105% the overload integrator starts. When falling below the integrator
counts backwards. If the integrator achieves the overload characteristic that corresponds to
the inverter, the error E.OL is triggered.
A.2

Overload protection in the lower speed range

(only operating mode MULTI and SERVO)
OC-tripping current
Short time current limit
Start of overload inte-
grator at 105%
Stand still current
(see technical data)
A PT1 element (τ = 280 ms) starts if the permissible current is exceeded. After its sequence of
operation the error E.OL2 is triggered.
GB - 32
Load [%]
E.OL2
170 180 190 200 210 220
Min. frequency at continuous full load
(see technical data)
Load [%]
E.OL
f [Hz]