648 Port InfiniBand FDR Switch Platform Hardware Installation Guide
Step 1.
Place the Cable holder next to the rack, on the connector side of the chassis,
and identify the holes where the caged nuts were placed in step 4
Step 2.
Set the bottom of the cable holder at the level of the shelf.
Step 3.
Screw the cable holder onto the rack using the screws provided.
Step 4.
Repeat steps 1- 3 for the second cable holder.
Mellanox Technologies
Figure 27: Cable Holder
The cable holders should go to the outside of the vertical supports.
If the cable holder is not set properly the upper bracket will not line up with the cable
holder.
Rev 1.4
Left side rack
Top side
16 X M6 caged nut
16 X M6 bolt for caged
nut
31