Smartgen HGM4020DC User Manual page 20

Genset controller
Table of Contents

Advertisement

No.
Items
8
Fan Off Temp
Aux. Sensor 2
1
Sensor Type
2
Curve Type
3
Open Act
4
Shutdown Value
5
Warn Value
Digital Input Ports
1
Input 1 Setting
2
Input 2 Setting
3
Input 3 Setting
4
Input 4 Setting
5
Input 5 Setting
HGM4020DC Genset Controller
HGM4020DC GENSET CONTROLLER USER MANUAL
Range
Default
(0-400) ℃
80
(0-3)
0
(0-10)
(0-10)
3
(0-5)
(0-2)
1
(0-400)
98
(0-400)
95
(0-31)
3
(0-1)
0
(0-20.0)s
2.0
(0-31)
9
(0-1)
0
(0-20.0)s
2.0
(0-31)
22
(0-1)
0
(0-20.0)s
2.0
(0-31)
0
(0-1)
0
(0-20.0)s
2.0
(0-31)
0
(0-1)
0
(0-20.0)s
2.0
Version 1.0
Description
open/close is based on the values.
0: Digital input 6;
1: Temperature sensor;
2: Oil pressure sensor;
3: Fuel level sensor;
Make a choice according to sensor type; for
details please see Table 13.
0: Indication (related sensor will show
"+++"); 1: Warn; 2: Shutdown.
Set this according to the sensor type; For
temp. sensor, if sampling value exceeds the
pre-set value, controller will initiate
shutdown alarms. If it is set as 140,
shutdown alarms will not be sent.
For oil pressure sensor and fuel level
sensor, if sampling value falls below the
pre-set value, controller will initiate
shutdown alarms. If it is set as 0, shutdown
alarms will not be sent.
Set this according to the sensor type; For
temp. sensor, if sampling value exceeds the
pre-set value, controller will initiate warning
alarms. If it is set as 140, warning alarms will
not be sent.
For oil pressure sensor and fuel level
sensor, if sampling value falls below the
pre-set value, controller will initiate warning
alarms. If it is set as 0, warning alarms will
not be sent.
Factory default: emergency stop alarm input,
for details please see Table 12.
0: close to activate; 1: open to activate.
It is time from detection of the input port is
active to action confirm.
Factory default: remote start (on load), for
details please see Table 12.
0: close to activate; 1: open to activate.
It is time from detection of the input port is
active to action confirm.
Factory default: door inhibit input, for details
please see Table 12.
0: close to activate; 1: open to activate.
It is time from detection of the input port is
active to action confirm.
Factory default: not used, for details please
see Table 12.
0: close to activate; 1: open to activate.
It is time from detection of the input port is
active to action confirm.
Factory default: not used, for details please
see Table 12.
0: close to activate; 1: open to activate.
It is time from detection of the input port is