Smartgen HGM4020DC User Manual page 23

Genset controller
Table of Contents

Advertisement

No.
Items
8
Preheat Control
9
Raise Speed
10
Drop Speed
11
Reserved
12
Reserved
13
Reserved
14
Reserved
15
Reserved
16
Reserved
17
Fuel Pump Control
18
High Speed Control
19
Crank Out
20
Fuel Out
21
Generator Excite
22
Advance Oil Output
23
Room Fan Control
24
Run Out
25
Timing Start
26
Charge Alt. Fail
27
In Auto Mode
28
In Manual Mode
29
In Stop Mode
High Room Temp
30
Warn
31
Mains Abnormal
32
Louvre Control
33
Battery Over Volt
34
Battery Under Volt
35
Tele. Open Door
36
Failed to Start
37
Pre-Oil
38
Fan Control
39
Reserved
40
Reserved
41
Reserved
42
Reserved
43
Reserved
44
Reserved
45
Reserved
46
Reserved
47
Reserved
48
Reserved
49
Reserved
50
Reserved
HGM4020DC Genset Controller
HGM4020DC GENSET CONTROLLER USER MANUAL
Close before start and open before power up;
Action while in hi-speed warming up running period.
Action while in the period time from stop idle speed to wait for stop.
Close when fuel level is lower than the "fuel pump on" value or when low
fuel level warning input is active; Open when fuel level is higher than the
"fuel pump off" value and low fuel level warning input is deactivated;
Close when the generator enters into warming up time and open after
cooling delay.
Output while engine is cranking.
Action at generator start; disconnect at "wait for stop".
Output in start period. If there is not generator frequency during
high-speed running, it shall output for 2 seconds again.
Output while genset is between the periods from pre-heat to stop idle
speed.
Output is controlled according to the upper/lower limit of the engine
room temperature.
Output while genset is between periods from normal running to hi-speed
cooling.
Output while genset is in the period of scheduled start.
Output when charger fails to charge the batteries.
Action while system is in auto mode.
Action while system is in manual mode.
Action while system is in stop mode.
When temperature of machine room reaches the "room high temp warn"
limit, alarms will be initiated.
Action when mains over/under frequency, over/under voltage or aux.
mains abnormal input is active.
Action when genset starts up and disconnect after genset stops and
"louver hold open" time is expired.
Output when battery voltage high warning occurs.
Output when battery voltage low warning occurs.
This output is remotely controlled by Modbus-RTU protocol, and output
time is "Telecontrol Open Door Output Time".
Output when engine fails to start.
Output while genset is between periods from pre-heat to safety running.
It is controlled by fan open and fan close according to temperature value
of temp. sensor selected for programmable sensor 1.
Version 1.0
Function Description
2019-04-10
Page 24 of 31