Smartgen HGM4020DC User Manual page 13

Genset controller
Table of Contents

Advertisement

No.
Type
Temp 1 Open
20
Shutdown
Pressure 2 Open
21
Shut.
Level 2 Open
22
Shutdown
Temp 2 Open
23
Shutdown
Pressure 3 Open
24
Shut.
Level 3 Open
25
Shutdown
High Temp. 1
26
Shutdown
Low Pressure 2
27
Shutdown
Low Fuel Level 2
28
Shutdown
High Temp. 2
29
Shutdown
Low Pressure 3
30
Shutdown
Low Fuel Level 3
31
Shutdown
HGM4020DC Genset Controller
HGM4020DC GENSET CONTROLLER USER MANUAL
corresponding alarm information will be displayed on LCD.
When controller detects temp. sensor, which connects to programmable
sensor 1, is open circuit, and the action selects "shutdown", it will send
stop signals and the corresponding alarm information will be displayed
on LCD.
When controller detects pressure sensor, which connects to
programmable sensor 1, is open circuit, and the action selects
"shutdown", it will send stop signals and the corresponding alarm
information will be displayed on LCD.
When controller detects fuel level sensor,which connects to
programmable sensor 1, is open circuit, and the action selects
"shutdown", it will send stop signals and the corresponding alarm
information will be displayed on LCD.
When controller detects temp. sensor, which connects to programmable
sensor 2, is open circuit, and the action selects "shutdown", it will send
stop signals and the corresponding alarm information will be displayed
on LCD.
When controller detects pressure sensor, which connects to
programmable sensor 2, is open circuit, and the action selects
"shutdown", it will send stop signals and the corresponding alarm
information will be displayed on LCD.
When controller detects fuel level sensor,which connects to
programmable sensor 2, is open circuit, and the action selects
"shutdown", it will send stop signals and the corresponding alarm
information will be displayed on LCD.
When controller detects the sample value, which adopted by the
programmable sensor 1(sensor type is temp. sensor), is higher than the
pre-set value, it will send stop signals and the corresponding alarm
information will be displayed on LCD.
When controller detects the sample value, which adopted by the
programmable sensor 1(sensor type is pressure sensor), is lower than
the pre-set value, it will send stop signals and the corresponding alarm
information will be displayed on LCD.
When controller detects the sample value, which adopted by the
programmable sensor 1 (sensor type is level sensor), is lower than the
pre-set value, it will send stop signals and the corresponding alarm
information will be displayed on LCD.
When controller detects the sample value, which adopted by the
programmable sensor 2(sensor type is temp. sensor), is higher than the
pre-set value, it will send stop signals and the corresponding alarm
information will be displayed on LCD.
When controller detects the sample value, which adopted by the
programmable sensor 2(sensor type is pressure sensor), is lower than
the pre-set value, it will send stop signals and the corresponding alarm
information will be displayed on LCD.
When controller detects the sample value, which adopted by the
programmable sensor 2 (sensor type is level sensor), is lower than the
pre-set value, it will send stop signals and the corresponding alarm
information will be displayed on LCD.
Version 1.0
Description
2019-04-10
Page 14 of 31