Resettable Power; On-Board Relays (Conventional); Trouble Relay; Programmable Relays - Honeywell Silent Knight IntelliKnight 5820XL Installation And Operation Manual

Addressable fire system
Table of Contents

Advertisement

IntelliKnight 5820XL Installation Manual

4.13.5.3 Resettable Power

Resettable power is typically used to power beam detectors, flame detectors and conventional
4-wire smoke detectors. For circuits selected as Resettable, 24-volt power is always present at
the terminals unless a system reset occurs. If a system reset occurs, power is disconnected
from the terminals for 30 seconds, then re-applied.

4.14 On-Board Relays (Conventional)

The control panel has two built-in programmable relays and a built-in trouble relay. All relays
are Form C rated at 2.5 A @ 24 VDC.
Figure 4-39 Location of Conventional Relay Circuits

4.14.1 Trouble Relay

The control panel has a dedicated Form C trouble relay built into terminals 30-32. The relay
provides a normally open and a normally closed contact. The trouble relay will deactivate
under any trouble condition.
Note: The N.C. contact is the relay contact that is closed when the panel has power and there are no trouble con-
ditions.

4.14.2 Programmable Relays

The control panel has two Form C programmable relays built into terminals 24-29. Each relay
provides a normally open and a normally closed contact.
To install one or two programmable relays, follow these steps.
1. Wire Relay 1 and/or Relay 2 as needed for your application. See Figure 4-39 for the loca-
tion of the relay terminals.
2. Configure the relay through programming (see Section 7.5).
4-40
firealarmresources.com
151209

Advertisement

Table of Contents
loading

Table of Contents