10.3.2 SLC Multi Locator

This feature is the same as SLC Device Locator, except you can locate up to 8 devices on a
single search.
Follow these instructions to locate multiple SLC devices:
1. Select
(Point Functions) from the Main Menu.
2
2. Select
(SLC Dev Locator).
5
A message similar to the one shown in Figure 10-1 will display.
3. Press the
or
If NO is chosen you will exit back to the Point Function menu.
If Yes is chosen the system will cease normal operation leaving the premise unprotected.
4. Select the SLC loop.
5. Enter up to 8 SLC addresses for the devices you wish to locate.
The LEDs on the selected devices will start flashing.
6. Press the
to exit SLC multi-locator function.
Note: Once you exit the system will resume normal operation.