Honeywell Silent Knight SK318PT Installation And Operation Manual

Honeywell Silent Knight SK318PT Installation And Operation Manual

Addressable fire system, emergency voice system
Table of Contents

Advertisement

6820 / 6820EVS
Addressable Fire System
Emergency Voice System
Installation and Operation Guide
Document LS10144-001SK-E Rev: C
10/9/2017 ECN: 17-0555

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell Silent Knight SK318PT

  • Page 1 6820 / 6820EVS Addressable Fire System Emergency Voice System Installation and Operation Guide Document LS10144-001SK-E Rev: C 10/9/2017 ECN: 17-0555...
  • Page 2 Fire Alarm & Emergency Communication System Limitations While a life safety system may lower insurance rates, it is not a substitute for life and property insurance! An automatic fire alarm system—typically made up of smoke Heat detectors do not sense particles of combustion and alarm detectors, heat detectors, manual pull stations, audible warning only when heat on their sensors increases at a predetermined rate devices, and a fire alarm control panel (FACP) with remote notifica-...
  • Page 3 Installation Precautions Adherence to the following will aid in problem-free installation with long-term reliability: WARNING - Several different sources of power can be Like all solid state electronic devices, this system may connected to the fire alarm control panel. Disconnect all operate erratically or can be damaged when subjected to light- sources of power before servicing.
  • Page 4 To order parts, contact Silent Knight Sales at 800-328-0103. eVance®, Honeywell®, Silent Knight®, and SWIFT® are registered trademarks of Honeywell International Inc. Microsoft® and Windows® are registered trademarks of the Microsoft Corporation. Chrome™ and Google™ are trademarks of Google Inc. Firefox® is a registered trademark of The Mozilla Foundation.
  • Page 5: Table Of Contents

    Contents 1.1: Overview of Basic System....................................8 1.1.1: Addressable Fire Alarm Control/Communicator Hardware Features ....................8 1.1.2: Common Communication / Annunciation Link System Hardware Features ..................8 1.1.3: Software Features ....................................8 1.1.4: 6820EVS Features ....................................8 1.2: About this Manual......................................9 1.2.1: Terms Used in this Manual..................................9 1.3: Compatible Products......................................9 2.1: Federal Communications Commission (FCC)..............................12 2.2: Underwriters Laboratories (UL) ..................................12...
  • Page 6 4.11: 5880 LED I/O Module ....................................50 4.11.1: 5880 Board Layout .....................................50 4.11.2: 5880 Connection to Panel...................................51 4.11.3: LED Wiring ......................................51 4.11.4: Dry Contact Wiring ....................................52 4.12: 5865-3 / 5865-4 LED Annunciator Installation .............................53 4.12.1: 5865 Connection to Panel...................................53 4.12.2: 5865 Mounting....................................54 4.13: Configuring SBUS Modules..................................54 4.13.1: Assigning SBUS Module IDs................................54 4.13.2: SBUS Bandwidth Considerations...............................55...
  • Page 7 Edit Name .......................................80 Edit Access Code ....................................80 Panel Functions.......................................80 6.2.6: Communicator Options..................................80 Communicator Assignments...................................80 Communicator Miscellaneous ................................80 Receiver Configuration...................................80 Communicator Reporting Table ................................81 6.3: Voice Options........................................81 6.3.1: Edit Timers ......................................81 Control Lockout......................................81 Auto Reset EVS MIC Triggered Event ..............................81 6.3.2: Edit Voice Commands..................................82 6.4: Sync Network Options.....................................83 Network Management Quick Reference ..............................85 7.1: List of SK SLC Devices ....................................88...
  • Page 8 9.4.1: Edit Group ......................................118 Edit Group Name ....................................118 Edit Group Properties ...................................118 9.4.2: View Group Points .....................................119 9.4.3: Edit OPG Template.....................................119 9.5: Point ..........................................120 9.5.1: Point Programming For 5815XL Module............................120 9.5.2: Point Programming For 6815 Module..............................122 9.5.3: Point Programming For Internal or External Power Module ......................124 9.5.4: Point Programming For 5880, 5865, EVS-50W, EVS-INT50W, EVS-100W, EVS-125W and EVS-CE4 Modules .......125 9.5.5: Point Programming For EVS-VCM and EVS-RVM Modules......................126 9.6: System Options......................................127...
  • Page 9 10.4.10: Check Detector Sensitivity Through Point Status .........................139 10.4.11: View Status of a Point ..................................140 10.4.12: View Alarms or Troubles ................................140 10.4.13: System Information ..................................140 10.5: Event Priority.......................................141 10.5.1: System Control ....................................141 10.5.2: System Override ....................................141 10.5.3: Event Priority....................................141 10.5.4: Priority Rules ....................................142 10.5.5: Other Priority Considerations ................................142 10.6: Operation Mode Behavior ...................................142 10.6.1: Multi-Site Annunciator and Multi-Site User Access........................145...
  • Page 10 11.7.4: Emergency Page ....................................156 11.7.5: Paging .......................................156 11.8: Recording Custom Messages..................................157 11.8.1: Recording Messages 1-15 Using Aux Audio Input ..........................157 11.8.2: Recording Messages 1-15 Using the Microphone..........................159 11.8.3: Erasing User Message..................................160 11.8.4: Using HFSS Voice Message Load Software ............................160 12.1: Receivers Compatible with the Control Panel.............................162 12.2: SIA / Panels PI Modifier Reporting:................................172 12.3: SIA –...
  • Page 11 6820 / 6820EVS Manual - P/N LS10144-001SK-E:C 09/28/2017...
  • Page 12: Overview Of Basic System

    Section 1: Introduction The 6820 Fire Alarm Control/Communicator is an addressable fire control system that meets the requirements of UL 864. The 6820EVS integrates an Emergency Voice System that meets the requirements of UL 864 and UL 2572. 1.1 Overview of Basic System The 6820 and 6820EVS base system is an addressable system with a built-in annunciator that can also be used to program the system.
  • Page 13: About This Manual

    6808, 6820, or 6820EVS. For reporting purposes only. Not a peer-to-peer networked system. SWIFT Smart Wireless Integrated Fire Technology 1.3 Compatible Products Table 1.1 lists the products available from Honeywell Silent Knight for use with the 6820 and 6820EVS. Type of Device Model Description SK Addressable See Section 7.1 for a list of compatible devices.
  • Page 14 Type of Device Model Description 5815XL (Rev H or higher) Allows an additional 127 SD devices to be added to the system for a maximum SLC Expander of 635 points. Supports SD devices only. 6815 SLC Expander Allows an additional 159 SK modules and 159 SK sensors to be added to the system for a maximum of 1110 points.
  • Page 15 Model Description 7860 Telephone Cord RJ31X cord for connecting phone line to the 6820/EVS. HFSS Honeywell Fire For communication and panel programming with a Windows-based computer. Software Suite Enables remote viewing of detector status and event history. Remote Battery Box for mounting backup batteries that are too large to fit into Misc.
  • Page 16: Federal Communications Commission (Fcc)

    If trouble is experienced with the 6820 or 6820EVS, for repair or warranty information, please contact Honeywell Silent Knight at 1- 800-328-0103 or www.silentknight.com. If the equipment is causing harm to the telephone network, the telephone company may request that you disconnect the 6820 or 6820EVS until the problem has been resolved.
  • Page 17: 2: Requirements For Central Station Fire Alarm Systems

    Use UL listed notification appliances compatible with the 6820 or 6820EVS from those specified in Appendix A of this manual. A full system checkout must be performed any time the panel is programmed. Restricted Options: • The loss of AC signal is defaulted to 3 hours, however the system allows settings from 0 - 30 hours. For UL certified installations this number must be set from 1 to 3 hours.
  • Page 18 Remote Mass Notification (In- Model/Module Description Local Auxiliary EVAC Station Building) 068200 Motherboard RA-100BD Control unit operator interface 00VIP-50CB Amplifier Enclosure 00VIP-125CB Amplifier Enclosure 122774 Control unit enclosure VIP/EVS-50W 50W Amp VIP/EVS-50WHV 50W Amp EVS-125W 125W amp EVS-125HV/VIP- 125W Amp 125HV EVS-INT50W Internal 50W...
  • Page 19 6820 / 6820EVS Manual P/N LS10144-001SK-E:C 10/09/2017...
  • Page 20: Inventory

    Contact Tech- nical Support with any questions about software and the appropriate version for a specific application. HFSS Honeywell Fire Software Suite software is available at www.silentknight.com.
  • Page 21: Electrical Specifications

    3.4 Electrical Specifications Rating Earth Ground Terminal Label Description Faults Voltage Current AC input (hot) 120 VAC, 60 Hz 3.3 A Earth ground AC input (neutral) 120 VAC, 60 Hz 3.3 A – NAC 6 Flexput™ Circuits 24 VDC 3.0A notification and auxiliary 0...
  • Page 22: Wiring Specifications

    Rating Earth Ground Terminal Label Description Faults Voltage Current Ring Phone Line 1 Telco Ring 0 Phone Line 1 Telco Tip Ring Phone Line 1 Premises Ring Phone Line 1 Premises Tip Ring Phone Line 2 Telco Ring 0 Phone Line 2 Telco Tip Ring Phone Line 2 Premises Ring Phone Line 2 Premises Tip...
  • Page 23 Figure 3.1 Wire Routing Example for 6820/EVS 6820 / 6820EVS Manual P/N LS10144-001SK-E:C 09/28/2017...
  • Page 24: Board Assembly Diagram

    3.6 Board Assembly Diagram AC Power Input Circuits Flexput Relays Trouble Relay SBUS In/Out Battery Phone Lines EXT. COMM Connection Figure 3.2 Model 6820/EVS Assembly Figure 3.2 shows the circuit boards and annunciator. If you should need to remove the control board for repair, do so by removing the nuts that hold the heat sink bracket to into the cabinet.
  • Page 25 6820 / 6820EVS control panel. If the current is above 6.0 A you will need to use a notification power expander(s) such as the Honeywell Silent Knight 5495 or the 5895XL intelligent power expander, to distribute the power loads so that the 6820 / 6820EVS or the power expanders do not exceed their power ratings.
  • Page 26: 2: Current Draw Worksheet For Sk Slc Devices

    3.7.2 Current Draw Worksheet for SK SLC Devices Use Table 3.2 to determine current requirements during alarm/battery standby operation SK SLC devices are installed. The 6820EVS FACP supports up to a total of 1110 SLC devices, consisting of any combination of Sensors and Modules. Standby Alarm Device...
  • Page 27 Standby Alarm Device # of Devices Current per Device Current Current Aux Pwr Standby 12mA SK-ZONE Alarm 90mA Standby/Alarm .27mA Aux Pwr Standby 50mA SK-ZONE-6 Alarm 270mA Standby/Alarm SLC Modules Standby: .5mA Aux Pwr B200SR-WH / IV Intelligent sounder base Alarm: 35mA Standby...
  • Page 28 Standby Alarm Device # of Devices Current per Device Current Current (4 max.) Standby: 100mA EVS-LOC Local Operating Console (includes 6860, RVM & SW-24) Alarm: 150mA EVS-100W 100W amplifier (4 max.) Standby/Alarm: 10mA EVS-100WBU backup daughter card (4 max.) Standby/Alarm: 10mA Total System Current Network Cards...
  • Page 29: 3: Current Draw Worksheet For Sd Slc Devices

    3.7.3 Current Draw Worksheet for SD SLC Devices Use Table 3.3 to determine current requirements during alarm/battery standby operation when SD SLC devices are installed. You can install up to 127 SD devices per loop. Standby Alarm Device # of Devices Current per Device Current Current...
  • Page 30 Standby Alarm Device # of Devices Current per Device Current Current EVS-50W or EVS-125W Audio Amplifier (4 max.) Standby: 10 mA with/without EVS-CE4 Alarm: 10 mA EVS-INT50W Internal Amplifier (4 max.) Standby: 52 mA Alarm @ 25V: 275 mA Alarm @ 70V: 310 mA EVS-VCM Voice Control Module (1max.)
  • Page 31: 4: Maximum Battery Standby Load

    WARNING: Honeywell Silent Knight does not support the use of batteries smaller than those listed in Table 3.4 and Table 3.5. If you use a battery too small for the installation, the system could overload the battery resulting in the installation having less than the required 24 hours standby power. Use Table 3.4 and Table 3.5 to calculate the correct battery amp hour rating needed for your installation.
  • Page 32: Mounting The Control Panel Cabinet

    Section 4: Control Panel Installation 4.1 Mounting the Control Panel Cabinet The 6820 cabinet can be surface or flush-mounted. Cabinet base dimensions are 14.5" W x 24.75" H. There should be 1.5" to 1.75" of cabinet extruding from the wall, this should be measured from either the top edge or bottom edge to the exterior side of the sheet rock. Do NOT flush mount in a wall designated as a fire break.
  • Page 33: Battery Power

    The AC terminals are rated at 120 VAC, 60 Hz, 2.7A. Figure 4.2 120 VAC Power Connection for the 6820 or 6820EVS 4.3 Battery Power The batteries must be sealed lead acid type. Before connecting the batteries to the FACP, make certain that the interconnect cable between the batteries is not connected.
  • Page 34: Installing The Rbb Accessory Cabinet And Batteries

    Installing the RBB Accessory Cabinet and Batteries To properly install the accessory cabinet and backup batteries, follow these steps: Mount the accessory cabinet. See Figure 4.4 for the four cabinet mounting holes. • If mounting onto drywall the accessory cabinet must be mounted onto 3/4-inch plywood. This is necessary because the weight of the batteries inside the accessory cabinet could cause the cabinet to pull away from the drywall.
  • Page 35: Sbus Wiring

    Run extended battery cable from control panel cabinet through conduit to RBB cabinet. See Figure 4.6. RBB Cabinet Cover Screws Conduit Coupler Conduit RBB Cabinet Cover Screws Figure 4.6 Battery Connections in the RBB Cabinet NOTE: Figure 4.6 is an example of how the wire connections can be routed. However, any other cabinet knock-outs (on either the main control panel or the RBB cabinet), that are not previously being used may be utilized to connect conduit between the two cabinets Connect battery leads to the backup battery terminals.
  • Page 36 To calculate the wire gauge that must be used to connect SBUS modules to the control panel, it is necessary to calculate the total worst case current draw for all modules on a single 4-conductor bus. The total worst case current draw is calculated by adding the individual worst case currents for each module.
  • Page 37 NOTE: The following formulas were used to generate the wire distance chart. Maximum Resistance (Ohms) = 6.0 Volts Total Worst Case Current Draw (amps) Maximum Wire Length (Feet) = Maximum Resistance (Ohms) * 500 (6000 feet maximum) where: Rpu = Ohms per 1000 feet for various wire gauges (see table below) Wire Gauge Ohms per 1000 feet (Rpu) 16.2...
  • Page 38: 2: Wiring Configurations

    4.4.2 Wiring Configurations Figure 4.8 illustrates Class A wiring configuration and Figure 4.9 illustrates Class B configuration. Caution For proper system supervision do not use looped wire under terminals marked A, B, +, and - of the SBUS device connectors. Break wire runs to provide supervision of connections.
  • Page 39: 5860 Remote Annunciator Installation

    4.5 5860 Remote Annunciator Installation The optional Model 5860 Remote Annunciator, is shown in Figure 4.10. Up to 16 annunciators can be added to the 6820 / 6820EVS sys- tem in any combination. Figure 4.10 Model 5860 Remote Annunciator, Front View 5860 installation involves the following steps: Make sure power is off at the panel.
  • Page 40: 1: Mounting The 5860

    4.5.1 Mounting the 5860 This section of the manual describes mounting the remote annunciator. The annunciator can be flush- or surface-mounted. Figure 4.11 shows the parts of the annunciator. Instructions for disassembling and mounting appear on the following pages. Figure 4.11 Annunciator Parts The 5860 comes from the factory fully assembled.
  • Page 41: Flush Mounting

    Flush Mounting This section of the manual describes flush mounting. You can flush-mount with or without an electrical box.  Flush Mounting with an Electrical Box The 5860 annunciator can be used with the following types of electrical boxes: 4S, single-gang, and double-gang. If an electrical box is used, the box must be 1-3/8”...
  • Page 42: Surface Mounting

    Surface Mounting The 5860 can be mounted directly to a surface or can be attached to a single, double, or four-square electrical box. The Model 5860TG/TR trim ring kit is available for use when surface mounting. Drill holes in the surface to match the screw holes on the back box. Fit the trim ring over the back box.
  • Page 43: 6855 Remote Annunciator Installation

    4.6 6855 Remote Annunciator Installation The optional Model 6855 Remote Annunciator, is shown in Figure 4.16. The 6855 can be surface or flush mounted. Up to 16 annuncia- tors can be added to the 6820 or 6820EVS system in any combination. Figure 4.16 Model 6855 Remote Annunciator, Front View 6855 installation involves the following steps: Make sure power is off at the panel.
  • Page 44  Follow these steps to flush mount the 6855 The back box dimensions are 9-9/32” W x 8-3/8” H. The minimum depth 2". The back box can be mounted prior to the complete installation of the 6855 using any of the mounting holes shown in Figure 4.17. Mounting Holes Mounting Holes Figure 4.17 Back Box Mounting Holes...
  • Page 45: Surface Mounting

    Attach the annunciator and door assembly to back box as shown in Figure 4.19 using the supplied screws. Figure 4.19 Attaching Annunciator/Door Assembly to Backbox Surface Mounting The optional Model RA-100TG/TR trim ring kit is available for use when surface mounting. Remove the desired knock out.
  • Page 46: 2: Model 6855 Connection To The Panel

    4.6.2 Model 6855 Connection to the Panel Connect the 6855 to the panel as shown in Figure 4.21. Supervised Power Limited Figure 4.21 Model 6855 Connection to the Panel 4.7 6860 Remote Annunciator Installation The optional Model 6860 Remote Annunciator, is shown in Figure 4.22. The 6860 can be surface or flush mounted. Figure 4.22 6860 Remote Annunciator, Front View 6860 installation involves the following steps: Make sure power is off at the panel.
  • Page 47: Flush Mounting

    Flush Mounting This section of the manual describes flush mounting. Follow these steps to flush mount the 6860 The back box dimensions are 9¼” W x 8 3/8” H. The minimum depth required is 2". The back box can be mounted prior to the complete installation of the 6860 using any of the mounting holes shown in Figure 4.23.
  • Page 48: Surface Mounting

    Attach the annunciator and door assembly to back box as shown in Figure 4.25 using the supplied screws. Figure 4.25 Attaching Annunciator / Door Assembly to Backbox Surface Mounting The Model RA-100TR red trim ring kit is available for use when surface mounting the 6860. Remove the desired knock out.
  • Page 49: 2: 6860 Connection To The Panel

    Place the trim ring over the back box as shown in Figure 4.27. Figure 4.27 Installing Trim Ring Attach the door assembly to the back box using screws provided. After the SBUS wiring to the annunciator is complete (described in Section Figure 4.7.2), replace the electronic assembly in the back box.
  • Page 50: 1: 5815Xl Connection To The Panel

    To install the 5815XL: Make sure power is off at the panel. Mount the 5815XL in the 6820 cabinet, the 5895XL cabinet, or the 5815RMK remote mounting kit. Use the standoffs located under the control panel board assembly and secure with screws provided with the 5815XL. For additional information, also see Model 5895XL Installation Instructions (P/N 151142) or 5815RMK Remote Mounting Kit Installation Instructions (P/N 151391).
  • Page 51: 6815 Installation

    4.9 6815 Installation The 6815 SLC expander lets you add 159 SK detectors and 159 SK modules. The maximum number of SLC devices per panel is 1110. The number of 6815’s is limited by the maximum number of SBUS devices. ®...
  • Page 52: 1: 6815 Connection To The Panel

    4.9.1 6815 Connection to the Panel Connect the 6815 to the control panel as shown in Figure 4.32. After the 6815 is connected to the panel, it must be added to the system. This programming step is described in Section 4.13. Supervised Power Limited Figure 4.32 6815 Connection to Main Panel Assembly...
  • Page 53: 1: Selecting 5824 Options

    Connect a printer to the 5824 as shown in Figure 4.33. Supervised Power Limited Figure 4.33 5824 Connection to the Panel 4.10.1 Selecting 5824 Options Configuring the 5824 includes the following steps: • Add the module to the system. JumpStart® will add the module automatically (see Section 8.1). You can also add it manually (see Section 9.2.2).
  • Page 54: 5880 Led I/O Module

    4.11 5880 LED I/O Module The 5880 is an LED driver board that can be used in a wide variety of applications, including as an interface with most customized floor plan annunciator boards. The 5880 can drive up to 40 LEDs and has one PZT controller. The 5880 also has eight inputs for monitoring dry contacts.
  • Page 55: 2: 5880 Connection To Panel

    4.11.2 5880 Connection to Panel The 5880 connects to the panel via the SBUS. Make connections as shown in Figure 4.36. After the 5880 is connected to the panel, it must be added to the system. This programming step is described in Section 4.13. Supervised Power Limited Figure 4.36 5880 Connection to Main Control Panel Assembly...
  • Page 56: 4: Dry Contact Wiring

    Figure 4.37 5880 Board Layout 4.11.4 Dry Contact Wiring The 8 input circuits on the 5880 board are for monitoring switch inputs-any type of switch supported by the control panel can be used with the 5880. For example, you can use a 5880 to monitor pull stations, water flow, tamper, reset, or silence switches. Wire dry contacts as shown in Figure 4.38.
  • Page 57: 5865-3 / 5865-4 Led Annunciator Installation

    4.12 5865-3 / 5865-4 LED Annunciator Installation The 5865-3 and 5865-4 are LED annunciators. The 5865-4 has 30 mappable LEDs, remote silence and reset key switches, and a general system trouble LED. The 5865-3 has 30 mappable LEDs only. These are arranged as 15 pairs of red (typically used for alarm) and yel- low (typically used for trouble) LEDs.
  • Page 58: 2: 5865 Mounting

    4.12.2 5865 Mounting Mount the 5865-4 to a standard 4-gang electrical box. Mount the 5865-3 to a standard 3-gang electrical box. In Figure 4.41, the 5865-4 attached to a 4-gang box is used as an example. Figure 4.41 5865 Mounting Example The 5865 ships with a set of zone description labels that can be inserted into the 5865 board assembly.
  • Page 59: 2: Sbus Bandwidth Considerations

    Each SBUS device generates a certain amount of traffic on the SBUS. Generally, the amount of traffic generated depends on the type of SBUS device. To help you figure out the SBUS bandwidth usage of a given collection of devices, a tool is available on the Honeywell Silent Knight website (www.silentknight.com).
  • Page 60: Telephone Connection

    4.14 Telephone Connection Connect the telephone lines as shown in Figure 4.44. The Model 7860 phone cord is available from Honeywell Silent Knight for this purpose. A number of programmable options are available for customizing telephone lines. These options are described in Section 9.6.
  • Page 61: 2: Class A Inputs

    Configure the circuit through programming (see Section 9.5). Supervised power limited UL Listed EOL 4.7 k Figure 4.45 Class B Input Switches 4.15.2 Class A Inputs You can connect conventional Class A switches, such as waterflow switches and pull stations, directly to the Flexput circuits of the con- trol panel.
  • Page 62: Installing 2-Wire Class B Smoke Detectors

    Installing 2-Wire Class B Smoke Detectors To install a Class B two-wire smoke detector, wire as shown in Figure 4.47. Supervised power limited Note: Flexput circuit 5 4.7 kEOL used as an example. Either Flexput circuit 5 or 6 could be used. Figure 4.47 Two-Wire Class B Smoke Detector Installing 2-Wire Class A Smoke Detectors To install a Class A two-wire smoke detector, wire as shown in Figure 4.48.
  • Page 63: Installing 4-Wire Class A Smoke Detectors

    The detector gets smoke power from Flexput 6 circuit and the contact input is connected to Flexput 5 circuit. 4.7 kEOL Air Products PAM-2 Model 160150 Supervision Module Supervised power limited Figure 4.49 Class B 4-Wire Smoke Detector Connections NOTE: In programming any point that uses multiple Flexput circuits, the lowest Flexput circuit number is used to refer to the circuit pair. In this example, Figure 4.49 uses both Flexput circuit 5 and 6, so in programming it would be referred to as point 5.
  • Page 64: 1: Class B Notification Wiring

    4.16.1 Class B Notification Wiring You must use an appliance from the list of compatible appliances in the Appendix A at the back of this manual. To install a Class B Notification appliance circuit: Wire Class B Notification appliances as shown in Figure 4.51. Configure the circuit through programming (see Section 9.5).
  • Page 65: 3: Auxiliary Power Installation

    Configure the circuit for Class A in programming (see Section 9.4.1). supervised power limited Regulated 24VDC Full Wave Rectified 27.4VDC, 3A per Circuit, 6A max Combined Figure 4.52 Class A Notification Appliance Circuit Configuration NOTE: In programming any point that uses multiple NAC circuits, the lowest circuit number is used to refer to the circuit pair. In this example, Figure 4.52 uses both NAC circuit 1 and 2, so in programming it would be referred to as point 1.
  • Page 66: Sounder Sync Power

    Sounder Sync Power Sounder Sync Power continuously outputs the System Sensor synchronization pattern and is intended for use with B200S sounder bases. 4.17 On-Board Relays (Conventional) The control panel has two built-in programmable relays and a built-in trouble relay. All relays are Form C rated at 2.5 A @ 24 VDC. Figure 4.53 Location of Conventional Relay Circuits 4.17.1 Trouble Relay The control panel has a dedicated Form C trouble relay built into terminals labeled TROUBLE.
  • Page 67: 2: City Box Connection Using The 5220 Module

    Program circuit 2 for supervisory non latching. Not suitable for remote station protected premises service where separate transmission circuits are required for fire supervisory (if applicable), and trouble signals. Intended for connection to a polarity rever- sal circuit of a remote station receiving unit having compati- ble ratings.
  • Page 68: 3: Using The Addressable Relay Module For City Box Connection

    It is not possible to reset the remote indication until you clear the condition and reset the control panel. All circuits non-power-limited All wiring non-supervised Figure 4.55 City Box Connection 4.18.3 Using the Addressable Relay Module for City Box Connection Wire the SK-Relay as shown in Figure 4.56.
  • Page 69: 4: Nfpa 72 Polarity Reversal

    4.18.4 NFPA 72 Polarity Reversal NOTE: Intended for connection to a polarity reversal circuit of a control unit at the protected premises having compatible rating. Using the 5220 Module When the 5220 is wired and programmed for polarity reversal, it reports alarm and trouble events to a remote site. Alarms will override trouble conditions and it will not be possible to reset the remote indicator until the condition is cleared and the control panel is reset.
  • Page 70: 5: Transmitter Activated By Dry Contacts

    Program the output group characteristics as non-silenceable and reverse polarity.. Figure 4.58 Polarity Reversal Connection Using the 7644-L8 4.18.5 Transmitter Activated by Dry Contacts This section describes the connection of a UL 864 listed remote station transmitter to the 6820/6820EVS FACP dry contacts. The FACP contacts must be supervised by the remote station transmitter module using end-of-line resistors (ELRs) with a value determined by the transmitter manufacturer.
  • Page 71 6820 / 6820EVS Manual P/N LS10144-001SK-E:C 09/28/2017...
  • Page 72: Hardware Features

    Section 5: Common Communication Link 5.1 Hardware Features 6820/EVS panels can be networked to create a virtual system that is larger than 1,110 addressable points. Each additional 6820/EVS pro- vides another 1,110 addressable points to the network total. For example, a network of 17- 6820/EVS panels provides a maximum addressable point capacity of 18,870 points (1,110 x 17 = 18,870 SK devices).
  • Page 73: Nic Wiring Options

    Figure 5.2 Internal SK-NIC Wiring Option 5.3 SK-NIC Wiring Options Linking a group of 6820/EVS requires the use of a SK-NIC network interface card with each panel. The SK-NIC connects to other linked units using unshielded, twisted-pair wiring or fiber-optic cable. Figure 5.3 SK-NIC Network Interface Card 6820 / 6820EVS Manual P/N LS10144-001SK-E:C 09/28/2017...
  • Page 74: 1: Fiber Loop Modules

    5.3.1 Fiber Loop Modules Two types of fiber optic modules are available to use to transmit and receive communication with the SK-NIC. See Figure 5.4. For more information see SK-FML / SK-FSL installation sheet P/N LS10178-001SK-E. SK-FML Multi-Mode Fiber SK-FSL Single-Mode Fiber Figure 5.4 Types Fiber Loop Modules The SK-FML (Fiber-Optic Multi-Mode) and SK-FSL (Fiber-Optic Single-Mode) are plug-in fiber loop modules.
  • Page 75 Use the 6-pin cable included with SK-NIC to connect the 6820/EVS to the SK-NIC. Connect the SK-NIC to the pin connector on the control panel labeled Data Network. See Figure 5.6. Data Network Figure 5.6 Panel to SK-NIC connection Each SK-NIC has the ability to monitor for earth ground faults on the twisted pairs connected to Port 1 of its terminal block TB2. Earth fault detection for any wiring at Port 2 of TB2 is done at the next/previous SK-NIC due to these wiring connections being connected to Port 1 of TB2 at the next/previous SK-NIC.
  • Page 76: Unshielded Twisted Pair Wiring Between Multiple Panels

    Unshielded Twisted Pair Wiring between Multiple Panels Unshielded twisted pair wiring between multiple panels is shown in Figure 5.7. Class A wiring is shown with a dotted line. Class A wiring Figure 5.7 Twisted Pair Wiring Configuration 6820 / 6820EVS Manual P/N LS10144-001SK-E:C 09/28/2017...
  • Page 77: Fiber Optic Multi-Mode Wiring Between Multiple Panels

    Fiber Optic Multi-Mode Wiring between Multiple Panels Fiber optic cable between multiple panels is shown in Figure 5.8. Class A is shown with a dotted line. Class A wiring Figure 5.8 Fiber Optic Wiring Example 6820 / 6820EVS Manual P/N LS10144-001SK-E:C 09/28/2017...
  • Page 78 Class A wiring Figure 5.9 Fiber Optic Wiring Single-Mode Example 6820 / 6820EVS Manual P/N LS10144-001SK-E:C 09/28/2017...
  • Page 79: Fiber Optic And Twisted Pair Wiring Between Multiple Panels

    Fiber Optic and Twisted Pair Wiring between Multiple Panels A mixture of fiber optic cable and twisted pair wiring between multiple panels is shown in Figure 5.10. Class A cabling is shown with dotted line. Class A wiring Figure 5.10 Twisted Pair and Fiber Optic Combination Wiring Example 6820 / 6820EVS Manual P/N LS10144-001SK-E:C 09/28/2017...
  • Page 80: Setting The Panel Id For Each Panel

    5.4 Setting the Panel ID for each Panel NOTE: It is important that much thought is given when choosing the panel IDs for each panel. It is difficult to change the IDs once panel programming has begun. The panel ID for each panel is set using DIP switch positions 1 through 5. See Figure 5.11 below for possible DIP switch settings. Figure 5.11 ID Settings 6820 / 6820EVS Manual P/N LS10144-001SK-E:C 09/28/2017...
  • Page 81 6820 / 6820EVS Manual P/N LS10144-001SK-E:C 09/28/2017...
  • Page 82: Network Diagnostics

    This section of the manual describes how to program network options using the built-in annunciator. All options described in this section can be programmed using the HFSS Honeywell Fire Software Suite. To edit site assignments, HFSS must be utilized. 6.2.1 Learn Network The Learn Network menu shows you all of the panels connected to the network.
  • Page 83: 4: Computer Access

    6.2.4 Computer Access An installer at the panel site can initiate communications between the panel and a computer running the HFSS Honeywell Fire Software Suite. In order for this communication to function properly, both the computer (running the software) and the control panel must have matching computer access numbers and computer codes.
  • Page 84: Edit Name

    To change an access code: Enter the installer code. The panel will automatically go to the main menu. Select 6 for Network Programming Menu. Select 5 for Access Codes. Display reads: Select Profile 01 Fire Fighter’s Key Select the access code you wish to edit by pressing the up or down arrow key. Then press ENTER.
  • Page 85: Communicator Reporting Table

    Available Format choices are: Reporting Format Contact ID SIA500 Ethernet Cellular eVance UNUSED SIA8 SIA20 Communicator Reporting Table The Communicator Report Table specifies event reporting for each panel on the communication link. Each row in the table specifies a panel, event types to report, primary and backup receiver numbers, and report by point or zone. Associated with the receivers are account number and daily test option.
  • Page 86: 2: Edit Voice Commands

    EVS Timer Option Control Lockout Immediate/Timer/Never Auto Reset EVS MIC Triggered Event Never/Timer/Event Disabled Auto Reset EVS Event 1 Never/Timer/Event Disabled Auto Reset EVS Event 2 Never/Timer/Event Disabled Auto Reset EVS Event 3 Never/Timer/Event Disabled Auto Reset EVS Event 4 Never/Timer/Event Disabled Auto Reset EVS Event 5 Never/Timer/Event Disabled...
  • Page 87: Sync Network Options

    System Event Fire Alarm Fire System Aux 1 Fire System Aux 2 Fire Zone Aux 1 Fire Zone Aux 2 Fire Pre Alarm Emergency Communication 1 Emergency Communication 2 Emergency Communication 3 Emergency Communication 4 Emergency Communication 5 Emergency Communication 6 Emergency Communication 7 Emergency Communication 8 Fire Supervisory...
  • Page 88 Select which panel to source the options from. With the line selected Line 1 scrolls to show the date Scroll down to show checksum Figure 6.2 Sync Network Options on a 6820 - 4 x 20 screen If 2 panels have the Last time the date &...
  • Page 89: Network Management Quick Reference

    Network Management Quick Reference Menu Options/Defaults Comments Add or remove Learn Guest or member panels into the See Section 6.2.1 Network network Edit Panel Names Network Panel ID Edit Panel Names Network See Section 6.2.2 Site Names Edit Site Member Edit Site Names Names Edit Panel...
  • Page 90 Menu Options/Defaults Comments Network Programming Panel Programming Profile 1 is the profile that System Information dictates what functions the Firefighter Key has access to. Multi-Site Because this is the profile for a Upload/Download keys, the user name and the F1 Function Key access code can not be edited Access Select Profile...
  • Page 91 Menu Options/Defaults Comments Immediate/ See Section 6.3.1 Control Lockout Timer/Neve Edit Timers Auto Reset EVS Never/Time Event 1-8 r/Event Auto Reset EVS MIC Disabled Triggered Event Fire Alarm Fire System Aux 1 Fire System Aux 2 Fire Zone Aux 1 Fire Zone Aux 2 Fire Interlock Release Voice...
  • Page 92: List Of Sk Slc Devices

    Section 7: SK, SD and SWIFT® Wireless SLC Device Installation CAUTION: To avoid the risk of electrical shock and damage to the unit, power should be OFF at the control panel while installing or servicing 7.1 List of SK SLC Devices The following SK and wireless SLC devices can be used with the control panel.
  • Page 93: List Of Sd Slc Devices

    Installation Model Name/Description Part Number Instruction PN SK-HEAT-W Fixed temperature thermal detector (135°F). White I56-6529-00 SK-HEAT-ROR-W Rate-of-rise thermal detector with 135° fixed temperature. White I56-6529-00 SK-HEAT-HT-W Fixed high temperature thermal detector (190°F). White I56-6529-00 Color Guide: -IV = Ivory color, -BL = Black, -WH = White, -WHITE-White Table 7.1 SK SLC Devices 7.2 List of SD SLC Devices The following SD SLC devices can be used with the control panel.
  • Page 94: Wiring Requirements For Slc Devices

    • SK SWIFT Wireless Devices–A SWIFT Gateway system supports up to 50 devices: 1 SWIFT Gateway and up to 49 (in any combination) wireless detectors and monitor modules. Multiple Gateways can be used. See the SWIFT manual P/N LS10036- 001SK-E for more information. 7.5 Wiring Requirements for SLC Devices The following information applies to all SLC devices.
  • Page 95 Figure 7.1 and Figure 7.2 show how wire length is determined for out & back tap and T-Tap. Figure 7.1 Calculating wire run length for a simple out and back When using T-taps, the total length of all taps and the main bus must not exceed 40,000 feet. This requirement must be met in addition to the maximum distance requirements for the various wire gauges.
  • Page 96: 4: Wiring 5815Xl Or 6815 In Class A Configuration

    7.5.4 Wiring 5815XL or 6815 in Class A Configuration Figure 7.3 illustrates how to wire the SLC loop for Class A installations. NOTE: Class A wiring also requires an isolator module as the first device on the in and the out loops. NOTE: No t-taps allowed on class A SLC loops.
  • Page 97: Wiring Sd Slc Detectors

    The control panel recognizes when an SK detector or SK module is installed. For this reason, SK detectors can be assigned any unique address from 1 to 159, and SK modules can be assigned any unique address from 1 to 159. There can be an SK detector using address 1 and an SK module using address 1.
  • Page 98 To address: Connect a detector base temporarily to the programming terminals as shown in Figure 7.7. (You can use the same base for each detector.) Figure 7.7 Temporary Connection of Detector Base to Panel for Addressing Enter the Installer code. The panel will automatically go to the main menu. Select 2 for Point Functions.
  • Page 99: 1: Slc Devices With Dip Switches

    7.9.1 SLC Devices with DIP Switches Input and relay module addresses are set using the DIP switches on the module board. The chart below shows the available addresses. For example, to select address 3, place DIP switches 1 and 2 in the up position. The range of valid addresses is 1-127. 0 is an invalid address.
  • Page 100: Jumpstart Autoprogramming

    Section 8: Programming Overview This section of the manual is intended to give you an overview of the programming process. Please read this section of the manual care- fully, especially if you are programming the control panel for the first time. ®...
  • Page 101: Mapping Overview

    Figure 8.1 is a brief overview of the concept of mapping. The next several pages of the manual show these subjects in detail. Figure 8.1 Mapping Overview NOTE: Mapping cannot be programmed through annunciators and can only be programmed through HFSS Honeywell Fire Software Suite. 6820 / 6820EVS Manual P/N LS10144-001SK-E:C 09/28/2017...
  • Page 102: 1: Input Point Mapping

    8.2.1 Input Point Mapping Input points are assigned to input zones, as the example in Figure 8.2 shows. Any input point can be assigned to any input zone. (Input points can be assigned to one zone only. An input point can be designated as “Unused,” which means it has not been assigned to a zone). Figure 8.2 Input Point Assignment Example 6820 / 6820EVS Manual P/N LS10144-001SK-E:C 09/28/2017...
  • Page 103: 2: Output Circuit Mapping

    8.2.2 Output Circuit Mapping Figure 8.3 is a simple example showing how to assign notification and relay output circuits to groups. For an example of a simple floor above/floor below application, see Figure 8.5. Figure 8.3 Example of Assigning Output Circuits to Groups 8.2.3 Event Mapping There are 11 types of Zone events 14 types of Panel events, and 6 types of Site events that can be mapped (see Table 8.1).
  • Page 104 System Zone Panel Site Trouble SBUS Expander Trouble General Trouble Status Point Active SBUS Class A Trouble Site Silenced SLC Loop Trouble Voice Aux In 1-8 Alarm AC Loss Trouble F1 Key Active Battery Trouble F2 Key Active Ground Fault Trouble F3 Key Active Phone Line Trouble F4 Key Active...
  • Page 105 Figure 8.5 Example of Zone Events Mapped to Output Groups and Patterns 6820 / 6820EVS Manual P/N LS10144-001SK-E:C 09/28/2017...
  • Page 106: 4: Mapping Led Points

    8.3 Programming Using the HFSS Software Suite You can use the HFSS Honeywell Fire Software Suite to program the control panel onsite (personnel will need to be onsite during the upload or download process). HFSS is a software package that lets you easily program the control panel using a Windows-based com- puter.
  • Page 107: 1: Entering / Exiting The Program Menu

    8.4.1 Entering / Exiting the Program Menu To enter Programming Menu: Enter the Installer Code (factory programmed default code is 123456). Then press 7. The menu option displays. See Section 9 for detailed menu information and Section 8.5 for a quick reference listing all programmable options and JumpStart defaults.
  • Page 108: Programming Menu Quick Reference

    8.5 Programming Menu Quick Reference This section of the manual lists all Program Menu options in the order they appear on the sub-menus. Default settings are indicated in text or marked with an asterisk (*). The comments column provide quick information and a reference to a section (if applicable) which has more detailed information.
  • Page 109 Menu Options/Defaults Comments Edit Zone Name Section 9.3.1 *1-Count 2-Count Alarm Ver. Verification Section 9.3.1 Type Zone SNGL ILOCK Properties DBL ILOCK SD devices 135° to 150°F Section 9.3.1 Heat Temp Edit Zone Select Zone SK Devices 135° to 190°F Zone Section 9.3.1 Single/...
  • Page 110 Menu Options/Defaults Comments UNUSED MANUAL PULL *LATCH WATERFLOW NON-LATCH *LATCH FIRE SUPERVSY NON-LATCH FIRE DRILL SILENCE RESET P.A.S. ACK *LATCH ZONE AUX1 NON-LATCH *LATCH SD and SK ZONE AUX2 NON-LATCH Devices on Internal and Select *LATCH SYSTEM 1,2,3, Point Enter Pt Section 9.5 SWITCH External 6815...
  • Page 111 Menu Options/Defaults Comments *LATCH EVS TAMPER 1,2,3, NON-LATCH SWITCH *LATCH EVS SUPER- VISORY NON-LATCH Select Module OUTPUT PT Select Group 1,2,3,4, AUX CONST NOTIF AUX RESET AUX DOOR OUTPUT PT Select Group 1,2,3,4,5,6 1,2,3,4, RELAY AUX RESET AUX DOOR LED Number 1-80 SLC LED Notif...
  • Page 112 Menu Options/Defaults Comments No Accessory SDR BAS 1,2,3,4,5 RLY BAS 1,2,3,4,5 HEAT 1,2,3,4,5 I-SdrBa (Intelligent Sounder 2,3,4 Base) No Accessory PHOTO 1,2,3,4,5 DUCT DCT RLY No Accessory SDR BAS RLY BAS ACCLIMATE I-SdrBa (Intelligent SD and SK DETECTOR Sounder Devices on 1,2,3,4,5 Base) Point...
  • Page 113 Menu Options/Defaults Comments No Accessory SDR BAS RLY BAS ALARM/FIRE I-SdrBA ALARM (Intelligent Sounder Base) No Accessory SDR BAS RLY BAS ALARM/FIRE I-SdrBA SUPR (Intelligent Sounder Base) 2,3,4 CO FIRE SD and SK No Accessory Devices on SDR BAS Point Internal and Select Enter Pt...
  • Page 114 Menu Options/Defaults Comments SLC LED LED Output LED Function (SD only) UNUSED NOTIF Select Group OUTPUT B NOTIF Super-vised CONTROL Yes or No CIRCUIT NOTIF Section 9.5 Select Group OUTPUT A NOTIF Super-vised CONTROL Yes or No CIRCUIT CON-STANT AUX RESET AUX PWR AUX DOOR AUX SYNC...
  • Page 115 Menu Options/Defaults Comments EVS TAMPER Latch and Non-Latch feature only appear for EVS SUPER- WATERFLOW,FIRE VISORY SUPERVISORY, FIRE TAMPER, ZONE AUX1, ZONE AUX2, SYSTEM AUX1, STATUS SYSTEM AUX2., EVS INPUT, POINT EVS TAMPER, and EVS SUPERVISORY Enter Pt /Select Function Select (cont.) Sensor...
  • Page 116 Menu Options/Defaults Comments Address Subn Mask Section Edit SubNet Edit Ethernet Ethernet Default Gateway DHCP Enable 75 sec, 90 Sec, 3 min, 5 Ethernet Supervise min, 1 hr, 24 *5 Minutes hrs, 30 days, None Communication 24Hrs, 30 Section Options Cellular Supervise *24 Hours AlarmNet Timers...
  • Page 117 Menu Options/Defaults Comments SYNC Strobes when Section Synchronize Strobes Silenced Active During Silence Miscellaneous Options Auto Display Events Section Auto Display Event Auto Daylight Saving Section Automatic Daylight System Time Savings Adjustment Options Daylight Saving cont Options DST Start Select week: 1st, 2nd, Section Daylight Saving Time Select month 3rd, 4th or Last...
  • Page 118: Ul 864 / Ul 2572 Programming Requirements

    This section of the manual describes how to manually program the control panel from the built-in annunciator. Each subsection discusses these menu options in detail. All options described in this section can be performed using HFSS Honeywell Fire Software Suite.
  • Page 119: Changing Module Options

    If you wish to edit the module’s name, press the ENTER on the modules name. Then press the number keys corresponding to the character to select each character for the module’s name (or press the right arrow to bypass editing the name). Press the right arrow to move to the next character.
  • Page 120: 1: Edit Zone

     Alarm Delay Characteristics The programmed zone type is provided for user reference only. To modify the zone type, use the HFSS Honeywell Fire Software Suite. Table 9.1 list the detector characteristics and a description of each. Type of Delay...
  • Page 121: Zone Accessory Options

    Type of Delay Description P.A.S.- Positive Alarm This option is intended to be used with an acknowledge switch. An alarm is delayed for 15 seconds, Sequence giving on-site personnel a chance to investigate the alarm. If the acknowledge switch is not activated within 15 seconds, an alarm occurs automatically.
  • Page 122: Group

    9.4 Group An output group is made up of output points that have been programmed to respond in the same way. Output groups simplify program- ming because you only have to program the output characteristics that are common to all of the group points once, instead of program- ming each individual point.
  • Page 123: 2: View Group Points

    Each of the output groups defined as voice can be mapped to a particular switch and LED on the EVS-VCM/ EVS-RVM and EVS- SW24. This allows the user to see the state of the voice groups assigned to the switches. This also lets the user individually select which areas they want to do a live page into.
  • Page 124: Point

    You can use words to display a descriptive name for a group. NOTE: See Appendix B for editing names. Right arrow to the OPG and select YES or NO to select which output groups to include in the template. 9.5 Point You may need to change characteristics of individual input points (detectors and switches) even after using JumpStart.
  • Page 125 Type Selection Function Latching Option Comments Positive acknowledge switch. This switch must be used in zones programmed as Positive Alarm Sequence (see , "Edit Zone Properties"). If an acknowledge switch closes when an alarm or trouble condition P.A.S. ACK is not already in progress, a trouble will occur. You must use a UL listed normally open, momentary switch type.
  • Page 126: 2: Point Programming For 6815 Module

    9.5.2 Point Programming For 6815 Module To program for points on an 6815 module, follow these steps: Enter the installer code. The panel will automatically go to the main menu. Select 7 for Panel Programming. Press 4 to enter point menu. Press the up or down arrow key to select the desired module.
  • Page 127 Type Selection Function Latching Option Comments MANUAL PULL Use this switch type for manual pull stations. This input is always latched. The switch can clear only when an alarm is reset. This switch type has the highest fire priority; it overrides any other type of fire alarm.
  • Page 128: 3: Point Programming For Internal Or External Power Module

    Type Selection Function Latching Option Comments EVS INPUT Latching User also has EVS Event Number 1-8 option for EVS INPUT. Non Latching Only available when an EVS-VCM is installed in the system. EVS TAMPER Latching Non Latching EVS SUPER- Latching SWITCH VISORY Non Latching...
  • Page 129: 4: Point Programming For 5880, 5865, Evs-50W, Evs-Int50W, Evs-100W, Evs-125W And Evs-Ce4 Modules

    10. Repeat steps 1 through 9 for all circuits. Function Selections Choices Type Selections Comments for each Type Enter Point Select Type UNUSED B NOTIF NOTIF Output Control Circuit A NOTIF AUX_PWR CONSTANT Constant auxiliary power. AUX RESET Resettable auxiliary power. AUX DOOR Door holder auxiliary power.
  • Page 130: 5: Point Programming For Evs-Vcm And Evs-Rvm Modules

    Press the up or down arrows to select the desired module. Refer to Section 8.5 for available choices. Then press ENTER. Select NOTIF or UNSED Select an output group for this Zone/Group Select a name for the Point Figure 9.5 Programming Points as Outputs for the 5880 Module Select Switch or Unused Select Function Figure 9.6 Programming Points as Inputs for the 5880 Module...
  • Page 131: System Options

    10. Repeat Steps 1 through 9 for all points. Function Selections for Choices Type Selections Comments each Type UNUSED MANUAL PULL WATERFLOW FIRE SUPERVISORY TAMPER FIRE DRILL SILENCE RESET Refer to comments column of PAS_ACK Table 9.5 for description of these ZONE AUX1 options.
  • Page 132 Number of Answer Rings This option is used in conjunction with the HFSS Honeywell Fire Software Suite. Use this option to determine the number of rings before the panel answers a call from the computer. Range is 00-15 rings. This option is factory-programmed as 06 rings, which should be compatible for most installations where the answering machine bypass feature is used.
  • Page 133: Edit Ethernet

    Answering Machine Bypass This option is used in conjunction with HFSS Honeywell Fire Software Suite. This feature ensures that an answering machine will not interfere with communication between the panel and the computer. If an answering machine is used at the panel site, enable this feature;...
  • Page 134: 2: Time Options

    • Dialing Gain: • Low = 9 DB Attenuation • Normal = 6 DB Attenuation • *High = 3 DB Attenuation • Reporting Gain: • *Low = 9 DB Attenuation • Normal = 6 DB Attenuation • High = 3 DB Attenuation 9.6.2 Time Options Through this programming option you can set the water flow delay time, alarm verification time, AC report delay, AC-Frequency, Auto- Resound, and Clock Format.
  • Page 135: 3: Miscellaneous Options

    9.6.3 Miscellaneous Options Through this programming option you can turn on or off strobe synchronization during silence and display status at idle (auto display event). To edit miscellaneous options: Enter the installer code. The panel will automatically go to the main menu. Select 7 for Program Menu.
  • Page 136: 6: Slc Family

    Select 7 for Edit Banner. NOTE: See Appendix B for instructions on how to edit the banner. Select each letter by pressing the up or down arrow, then press the right arrow to move to the next character. When done, press ENTER to move to line two of the custom banner. 9.6.6 SLC Family The 6820/6820EVS supports SD protocol SLC devices or SK protocol SLC devices.
  • Page 137: Restore Defaults

    9.8 Restore Defaults This option allows you to restore the panel back to factory defaults. All programming will be lost. Enter the installer code. The panel will automatically go to the main menu. Select 7 for Panel Programming. Select 7 for Restore Defaults. Press the up or down arrow key to select YES or NO from the warning screen.
  • Page 138: User And Installer Default Codes

    Section 10: System Operation Operation of the control panel is simple. Menus guide you step-by-step through operations. This section of the manual is an overview of the operation menus. Please read this entire section carefully before operating the panel. 10.1 User and Installer Default Codes Installer Code (factory-programmed as 123456).
  • Page 139: 1: Lcd Display

    Figure 10.2 shows the annunciator that is part of the control panel board assembly for the 6820EVS. Figure 10.2 Control Panel Annunciator for 6820EVS 10.2.1 LCD Display The control panel LCD displays system messages, annunciates alarms, supervisories and troubles, provides status information, and prompts for input.
  • Page 140: Menu System

    information on editing the banner. Text of Internal Banner Custom Banner Example Figure 10.4 Banner Display Examples for 6820EVS 10.3 Menu System The control panel is easy to operate from the Main Menu. To view the Main Menu press the ENTER or right arrow key on the control panel or remote annunciator.
  • Page 141: Disable / Enable Nacs By Template

    The panel can store up to 1000 events. When it reaches its 1000-event capacity, it will delete the oldest events to make room for the new events as they occur. In networked setups, each panel stores up to 1000 of its own events. When using HFSS Honeywell Fire Software Suite, all 1000 events from every panel in the network will be uploaded.
  • Page 142: 6: Conduct A Walk Test

    10.4.6 Conduct a Walk Test Walk Test is a feature which allows one person to test the fire alarm system. The Walk Test will run for 4 hours or until the user manually exits. If an alarm or pre-alarm condition is occurring in the system, you will not be able to enter the walk test. A walk test may only be initiated if the test is enabled in the user profile.
  • Page 143: 10: Check Detector Sensitivity Through Point Status

    • Fire Supervisory • Fire Pre-Alarm • CO Alarm • CO Supervisory • EVS Alarm • EVS Supervisory 10.4.10 Check Detector Sensitivity Through Point Status The control panel constantly monitors smoke detectors to ensure that sensitivity levels are in compliance with NFPA 72. Detectors are sampled every three hours.
  • Page 144: 11: View Status Of A Point

    Figure 10.6 Checking Detector Sensitivity Compliance 6820EVS 4x 40 display You can print detector status by uploading the detector status to and printing from HFSS Honeywell Fire Software Suite. 10.4.11 View Status of a Point From the Main Menu, select 2 for Point Status.
  • Page 145: Event Priority

    (LOC Mic Triggered EVS Alarm and LOC EVS 1 Alarm through LOC EVS 8 Alarm). By default, these events do not have a priority - they can be activated in any order. A programming option in HFSS Honeywell Fire Software Suite exists to force a priority scheme for the LOC EVS Alarm Events.
  • Page 146: 4: Priority Rules

    Emergency Voice Aux 4 Alarm CO Alarm Fire Pre-Alarm Fire Interlock Alert Emergency Supervisory Fire Supervisory CO Supervisory Trouble Site F Key Status System Status Table 10.1 : Event Priority Table NOTE: Status Points, Status Voice Aux 1, Status Voice Aux 2, and Background Music are contained within the System Status event priority. NOTE: All fire, emergency and system troubles are prioritized into the Trouble event priority 10.5.4 Priority Rules Event priorities can be changed only within, not between, priority levels (defined by bold lines in Table 10.1).
  • Page 147 Press the down arrow to view the location and type of alarm, supervisory, or trouble. If the panel is programmed to Auto Display Event, information describing the highest priority active event will display on the first two lines. The 3 and 4th line will show the status of which event types are active for each system (fire, CO and emergency systems).
  • Page 148 Operation In This Mode You Can Occurs When System Behavior Mode The communicator seizes control of the phone Press down arrow to view the supervisory condition. line and calls the central station. A screen similar to this one displays. The on-board annunciator sounds a loud, pulsing beep in the sequence one second on, one second off.
  • Page 149: 1: Multi-Site Annunciator And Multi-Site User Access

    Single Interlock Zone does not. An interlock switch is typically a dry-con- tact pressure switch. When Single or Double Interlock Zone releasing is selected using HFSS Honeywell Fire Software Suite software, the software suite will automatically default the following system parameters: NOTE: The defaults created can be modified through programming if desired.
  • Page 150 Rated Voltage, DC Rated Current, Milliamp T8210A107 24 VDC 8210G207 24 VDC Asco HV2740607 24 VDC HV2838521 24 VDC HV2740608 24 VDC Honeywell/Skinner 701X7028 24 VDC Barnbrook System EA45 24 VDC 890181 24 VDC 2000 486500 24 VDC Kidde Fenwal 895630...
  • Page 151: 1: Single Interlock Zone Releasing

    10.7.1 Single Interlock Zone Releasing A single interlock zone utilizes a minimum of two addressable detectors and a designated manual release switch. Important! Only addressable detectors can be used. No conventional detectors can be used. Each Single Interlock Zone input requires at least one manual release switch. ...
  • Page 152: Smoke Alarm Verification

     Conditions Required for a Release Output Activation Any release requires the activation of an interlock switch, and either a manual release switch or 2 activated addressable detectors. When these conditions are met, the “Release” and “General Alarm” outputs will activate, and the “Pre-Alarm” output will deactivate. Inputs Output Results 1st Addressable...
  • Page 153: 2: Aborting An F-Key Macro Recording Session

    This option is programmable for each output group map through HFSS Honeywell Fire Software Suite. When an F-Key is active and a map in the system is set to be disable by Map Inhibit, the system will show a trouble event indicating it as such.
  • Page 154: Overview

    Section 11: Emergency Voice System Operation 11.1 Overview The EVS series control panels and accessories provide features to meet the requirements for Mass Notification Systems as described in NFPA 72 and is compliant with the UL 2572 standard. EVS (Emergency Voice System) is integrated with the fire alarm and voice evac- uation functions of the control panel.
  • Page 155: Select Key Leds

    LOC Priority LOCs are assigned (through panel or HFSS Honeywell Fire Software Suite programming of the EVS-VCM or EVS-RVM) an LOC pri- ority of low, normal, or high. LOCs with a higher priority are always able to gain control from a lower priority LOC.
  • Page 156: User Profile Access Control

    Select Keys and will toggle on/off using the activation cadence assigned to it in output group pro- gramming. This is available in the panel and in HFSS Honeywell Fire Software Suite. See Section .
  • Page 157: 7: Passing Evs Control

    11.2.7 Passing EVS Control Passing of EVS Control is allowed when two LOCs have the same priority. When it is possible to pass control, a prompt (similar to Figure 11.2) will display in which the user can: request control from the LOC with EVS Control, enter an access code with the EVS Super User profile option to override the other LOC, or wait for the lockout timer to expire (if applicable).
  • Page 158: Evs Point Functionality

    11.4 EVS Point Functionality Any input point in the system can be configured as an EVS input. The Point EVS 1-8 Alarm input types can be used to trigger predeter- mined EVS events for output areas. EVS-VCM, or EVS-RVM points can be programmed to trigger Voice Aux events that can allow external audio to be played through the emergency system.
  • Page 159: 1: Adding An Loc

    11.6.1 Adding an LOC To add new LOCs to the system, follow these steps: Enter the installer code. The panel will automatically go to the main menu. Select 7 for Panel Program Menu. Press 1 to enter Module menu. Press 2 to add a module. From the next screen, add either an *EVS-VCM or **EVS-RVM.
  • Page 160: 4: Emergency Page

    If both the fire alarm and EVS are active and the active EVS event is programmed for higher priority than fire alarm; the user must also have gained EVS control. • In this case a fire page is NOT allowed at all and the LOC must gain EVS control in order to do any live voice. 11.7.4 Emergency Page An emergency page can occur when: Only the emergency system is active and the user has gained EVS Control.
  • Page 161: Recording Custom Messages

    The EVS-Series controls come with 15 recordable message slots. Message 1-15 can be recorded from the microphone, Aux Input or by using the HFSS Honeywell Fire Software Suite message management utility. All messages can be a maximum of one minute.
  • Page 162 Wire a speaker cable with 1/8” mini plug (Radio Shack Cat. No. 42-2454) to the Aux AUDIO GND and IN terminals. Refer to Figure 11.5. Plug in here Figure 11.5 AUX Audio Connection for Recording Plug the mini plug into the Line Out/Headphone jack on a PC or laptop. See Figure 11.5. Enter programming mode at main control panel.
  • Page 163: 2: Recording Messages 1-15 Using The Microphone

    Pressing Select Key 2 will start a playback of the recorded message. Press EVS Message Key 1 to enter message slot selection mode Press EVS Press Message Key 3 Select Key 2 to start and stop to record recording from Message to the Aux Audio this slot...
  • Page 164: 3: Erasing User Message

    Pressing Select Key 5 will start a playback of the recorded message. Press EVS Message Key to enter message slot selection mode Press Select Key 5 to record to this message slot Figure 11.7 Recording with Microphone Example 11.8.3 Erasing User Message To erase the message stored in switch 1-15 memory location follow these steps: Enter programming mode at main control panel.
  • Page 165 Select “Read from Panel” to read a message and store onto your hard drive, or “Write to Panel” to transfer a .SKE1 formatted message to the panel. Select the appropriate message location you wish to read/write. Enter the file name you wish to transfer (Press “Browse” to display a list of files.) Press “Start”...
  • Page 166: Receivers Compatible With The Control Panel

    Manufacturer Model Format Silent Knight by Model 9800 SIA and Contact ID Honeywell Model 9000 (SIA formats) Honeywell Security AlarmNet 7810-ir IP and Cellular Receiver, Contact ID only Ademco MX8000 SIA and Contact ID Ademco Model 685 (Contact ID )
  • Page 167 SIA Reporting Format Contact ID Reporting Format SIA pi Modifier Event Description Module Parameter Fixed Length Qualifier Event Group # Contact # ID # (If Event Format NN - Code Any) Codes panel ID XX- SBUS ID ZZZ- Zone # PPPP- Point # GGG- Group # E- Emergency #...
  • Page 168 SIA Reporting Format Contact ID Reporting Format SIA pi Modifier Event Description Module Parameter Fixed Length Qualifier Event Group # Contact # ID # (If Event Format NN - Code Any) Codes panel ID XX- SBUS ID ZZZ- Zone # PPPP- Point # GGG- Group # E- Emergency #...
  • Page 169 SIA Reporting Format Contact ID Reporting Format SIA pi Modifier Event Description Module Parameter Fixed Length Qualifier Event Group # Contact # ID # (If Event Format NN - Code Any) Codes panel ID XX- SBUS ID ZZZ- Zone # PPPP- Point # GGG- Group # E- Emergency #...
  • Page 170 SIA Reporting Format Contact ID Reporting Format SIA pi Modifier Event Description Module Parameter Fixed Length Qualifier Event Group # Contact # ID # (If Event Format NN - Code Any) Codes panel ID XX- SBUS ID ZZZ- Zone # PPPP- Point # GGG- Group # E- Emergency #...
  • Page 171 SIA Reporting Format Contact ID Reporting Format SIA pi Modifier Event Description Module Parameter Fixed Length Qualifier Event Group # Contact # ID # (If Event Format NN - Code Any) Codes panel ID XX- SBUS ID ZZZ- Zone # PPPP- Point # GGG- Group # E- Emergency #...
  • Page 172 SIA Reporting Format Contact ID Reporting Format SIA pi Modifier Event Description Module Parameter Fixed Length Qualifier Event Group # Contact # ID # (If Event Format NN - Code Any) Codes panel ID XX- SBUS ID ZZZ- Zone # PPPP- Point # GGG- Group # E- Emergency #...
  • Page 173 SIA Reporting Format Contact ID Reporting Format SIA pi Modifier Event Description Module Parameter Fixed Length Qualifier Event Group # Contact # ID # (If Event Format NN - Code Any) Codes panel ID XX- SBUS ID ZZZ- Zone # PPPP- Point # GGG- Group # E- Emergency #...
  • Page 174 SIA Reporting Format Contact ID Reporting Format SIA pi Modifier Event Description Module Parameter Fixed Length Qualifier Event Group # Contact # ID # (If Event Format NN - Code Any) Codes panel ID XX- SBUS ID ZZZ- Zone # PPPP- Point # GGG- Group # E- Emergency #...
  • Page 175 SIA Reporting Format Contact ID Reporting Format SIA pi Modifier Event Description Module Parameter Fixed Length Qualifier Event Group # Contact # ID # (If Event Format NN - Code Any) Codes panel ID XX- SBUS ID ZZZ- Zone # PPPP- Point # GGG- Group # E- Emergency #...
  • Page 176: Sia / Panels Pi Modifier Reporting

    12.2 SIA / Panels PI Modifier Reporting: Events are sent to the central station as a variable length string: The event format is: EEZZZZ Where: Event code (2 characters) ZZZZ Event parameter (up to four digits – not zero filled) The account number is sent using an account block that is separate from the event block Multiple events can be sent within a single event block.
  • Page 177 information) The Event field will contain 10 digits including the 2 digit event code (EE), 2 digit panel ID (PP), 2 digit Module Number (MM) and a 4 digit Event Parameter (ZZZZ). Based on the actual Event Code, the Module Number or Event Parameter fields might not contain pertinent information. In that case the field will contain zeros.
  • Page 178: Troubleshooting

    This section of the manual offers suggestions for troubleshooting hardware problems. Please read this section if you encounter a problem when installing the control panel. If these suggestions do not solve your problem or if you encounter a problem that is not listed here, contact Honeywell Silent Knight Technical Support at 800-446-6444 for assistance. Common Problems...
  • Page 179: Periodic Testing And Maintenance

    Problem Possible Cause / Suggested Actions Check the status of the 6815 green LED. If it flashes in the pattern .5 sec. on / .5 sec. off, it is likely that the 6815 has not been added to the system through programming.
  • Page 180: 2: Slc Multiple Locator

    Press the up or down arrow to toggle NO to YES then press ENTER. If NO is chosen you will exit back to the Point Function menu. If Yes is chosen the system will cease normal operation leaving the premise unprotected. Select the SLC loop.
  • Page 181: 4: Earth Fault Resistance

    13.4.4 Earth Fault Resistance Table 13.1 lists the earth fault resistance detection for each applicable terminal on the FACP. Terminal Label Low Biased High Biased Terminal Function Number (Values in Ohms) High High Trip Restore Trip Restore Flexput™ I/O 6 Notification –...
  • Page 182: Detector And Module Point Record

    Section 14: Installation Records This section of the manual is for you to use if you wish to track of how points, zones, and groups have been programmed. 14.1 Detector and Module Point Record If installing SK SLC devices, use Table 14.1 to record detector points (up to 99 per SLC loop) installed on the on-board SLC loop and make a copy of Table 14.2 to record installed modules (up to 99 per SLC loop).
  • Page 183 Zone / Module Addr Description Module Addr Zone/ Group Description Group On-board On-board On-board On-board On-board On-board On-board On-board On-board On-board On-board On-board On-board On-board On-board On-board On-board On-board On-board On-board On-board On-board On-board On-board On-board On-board On-board On-board On-board On-board On-board On-board...
  • Page 184 Zone / Module Addr Description Module Addr Zone/ Group Description Group Table 14.2 : Installation Record of Devices Installed on 5815XLs  Additional SLC Devices Use the table below to record devices installed on additional SLC expanders. Make a copy of this page if additional pages are needed. Zone / Module Addr...
  • Page 185 Zone / Module Addr Description Module Addr Zone/ Group Description Group Table 14.3 : Installation Record of Devices 6820 / 6820EVS Manual P/N LS10144-001SK-E:C 09/28/2017...
  • Page 186: A.1: Notification Appliances

    Appendix A: Compatible Devices A.1 Notification Appliances For proper operation, you must use polarized devices with a 4.7k ohm EOL resistor on each loop. All supervised notification appliances used with the control panel must be polarized. NOTE: Not all devices can use the Sync feature, be sure to check table below to ensure the device you have chosen will work with this feature.
  • Page 187 Manufacturer Model Audio Visual Type HC12/24W-FC Horn HC12/24K-FC Horn P2415-FC Horn/Strobe P2415W-FC Horn/Strobe P2415K-FC Horn/Strobe P241575-FC Horn/Strobe P241575W-FC Horn/Strobe P241575F-FC Horn/Strobe P241575K-FC Horn/Strobe P2430-FC Horn/Strobe P2430W-FC Horn/Strobe P2430K-FC Horn/Strobe P2475-FC Horn/Strobe (cont.) P2475W-FC Horn/Strobe P2475K-FC Horn/Strobe P24110-FC Horn/Strobe P24110W-FC Horn/Strobe P24110K-FC Horn/Strobe S2430W-FC...
  • Page 188 Manufacturer Model Audio Visual Type GEC-24-15 Horn/Strobe GEC-24-30 Horn/Strobe GEC-24-60 Horn/Strobe GEC-24-75 Horn/Strobe GEC-24-177 Horn/Strobe GEC-24-110 Horn/Strobe GEC-24-15/75 Horn/Strobe GX91 MiniHorn Steady Tone GX93 MiniHorn Temporal Tone HG124 Horn HS24-15 Horn/Strobe HS24-30 Horn/Strobe HS24-60 Horn/Strobe HS24-75 Horn/Strobe HS24-110 Horn/Strobe HS24-1575 Horn/Strobe GCC24 Multi Candella Horn/Strobe Ceiling Mount...
  • Page 189 Manufacturer Model Audio Visual Type Chime Chime CHSR 2-Wire Chime/Strobe CHSW 2-Wire Chime/Strobe Horn Horn Horn Horn WHT Wall 4x4 Horn Red Wall 4x4 HGRL Horn Red Wall 2x4 HGWL Horn WHT Wall 2x4 CHWL Chime WHT Wall 4x4 CHRL Chime Red Wall 4x4 CHSRL Chime/Strobe Red Wall 4x4...
  • Page 190 Manufacturer Model Audio Visual Type 4-Wire Horn/Strobe PC4W 4-Wire Horn/Strobe P4WH 4-Wire Horn/Strobe High Candela PC4WH 4-Wire Horn/Strobe High Candela P4RK 4-Wire Horn/Strobe PC4RK 4-Wire Horn/Strobe P4RHK 4-Wire Horn/Strobe High Candela PC4RHK 4-Wire Horn/Strobe High Candela PC4RH 4-Wire Horn/Strobe High Candela P2RL, P2RL-P, P2RL-SP* Horn/Strobe 2W Red Wall 4x4 P2WL, P2WL-P, P2WL-SP*...
  • Page 191 Manufacturer Model Audio Visual Type HW-LF Low Frequency Sounder SEP-SPSWL** Universal Expander Plate, Amber Lens, System White, ALERT Sensor SEP-SPSWL-P** Universal Expander Plate, White, Plain (cont.) SEP-BBSWL** Universal Expander Plate Back Box Skirt, White * P=Plain, ALERT=Pad Printing ALERT, SP=Fuego ** Expander plates are for vertical wall mounting only.
  • Page 192 Manufacturer Model Audio Visual Type HS-24 Horn HS4-241575W Horn/Strobe HS4-24MCW Horn/Strobe HS4-24MCWH Horn/Strobe HS4-24MCC Horn/Strobe MIZ-24S Mini Horn Strobe MT-121575W MultitoneHorn Strobe MT-241575W Multitone Horn Strobe MT-24MCW Multitone Horn Strobe MTWP-2475W Multitone Horn Strobe MTWP-2475C Multitone Horn Strobe MTG-121575W Multitone Horn Strobe MTR-121575W Multitone Horn Strobe MTWPA-2475W...
  • Page 193: A.2: Two Wire Detectors

    Manufacturer Model Audio Visual Type RSSR-2475W Strobe RSSR-2475C Strobe RSSR-24110C Strobe RSSA-24110W Strobe RSSB-24110W Strobe RSSG-24110W Strobe RSSR-24110W Strobe RSSA-24MCC Multi-Cd Strobe RSSB-24MCC Multi-Cd Strobe RSSG-24MCC Multi-Cd Strobe RSSR-24MCC Multi-Cd Strobe RSSWPA-2475W Strobe Weatherproof RSSWPA-24MCCH Strobe Weatherproof RSSWPG-24MCCH Strobe Weatherproof RSSWPR-24MCCH Strobe Weatherproof RSSWP-2475W...
  • Page 194 Model Name or Number Compatibility ID Manufacturer (Base model name or number in # per Loop Head Base parenthesis.) Apollo 55000-350 (45681-200) 55000-350 45681-200 15 / loop 55000-250 (45681-200) 55000-250 45681-200 24 / loop 55000-225 55000-225 45681-255, 256 15 / loop for Ion Detectors 55000-226 55000-226...
  • Page 195: A.3: Four-Wire Smoke Detectors/Devices (Ul Listed)

    A.3 Four-Wire Smoke Detectors/Devices (UL Listed) Max Standby Alarm Current Smoke Detector/Base Detector Type Current (mA) (mA) Fenwal CPD-7021 (w/70-201000-005 Base) Ionization 0.10 Fenwal PSD-7125 Photoelectric 0.10 Fenwal PSD-7126 (w/70-201000-005 Base) Photoelectric 0.10 Fire-Lite BLP-12-4W Base Gentex 824 Photoelectric 0.50 Gentex 824T Photoelectric 0.50...
  • Page 196: A.4: Door Holders (Ul Listed)

    Max Standby Alarm Current Smoke Detector/Base Detector Type Current (mA) (mA) System Sensor RRS-MOD Reversing Relay/Sync Module System Sensor 6424 Projected Beam 28.4 System Sensor Beam 1224(S) Projected Beam 38.5 * Contact manufacturer for current draws Table 17: Compatible Four-Wire Smoke Detectors A.4 Door Holders (UL Listed) The below table lists door holders that are compatible with the fire control panel.
  • Page 197: A.6: Compatible 520Hz Signaling Speakers

    A.6 Compatible 520Hz Signaling Speakers Model Number Description System Sensor Model Number Description Wall High-Fidelity Speaker, Red Wall High-Fidelity Speaker, White SPCR Ceiling High-Fidelity Speaker, Red SPCW Ceiling High-Fidelity Speaker, White SPSR Wall High-Fidelity Speaker Strobe, Red SPSRH Wall High-Fidelity Speaker Strobe, High Candela, Red SPSW Wall High-Fidelity Speaker Strobe, White SPSCR...
  • Page 198: B.8: Characters Used For Editing Text

    Appendix B: Editing Text Using the Built-In Programmer This section contains tables of programmable characters that may be used for device, module, site, template, group, and zone names or phone numbers. T9 style editing is used. B.8 Characters Used for Editing Text “Character Table”...
  • Page 199 6820 / 6820-EVS P/N LS10144-001SK-E:SKRev mm/dd/yyyy...
  • Page 200 Appendix C: Expanded Receiver/Panel Relationship The available receiver number will correspond with what panel number you entered. Receiver numbers are populated based on panel number and audited to allow only the 4 appropriate receivers. See Section 6.2.6. Panel Available receiver numbers Table C.1 Receiver/panel relationship P/N LS10144-001SK-E:SKRev mm/dd/yyyy 6820 / 6820-EVS...
  • Page 201 6820 / 6820-EVS P/N LS10144-001SK-E:SKRev mm/dd/yyyy...
  • Page 202 Appendix D: Cadence Patterns The cadence patterns shown in Appendix D are available for use with the control panel. Figure D.2 Cadence Patterns Available with the Control Panel P/N LS10144-001SK-E:SKRev mm/dd/yyyy 6820 / 6820-EVS...
  • Page 203 6820 / 6820-EVS P/N LS10144-001SK-E:SKRev mm/dd/yyyy...
  • Page 204: Panel Security

    Panel Security Panel installation / maintenance security checklist System Description: ________________________________________________________________ System Location: __________________________________________________________________ Installer: _________________________________________________ Date: __________________ Complete the following Cyber security tasks for each panel Install • Install the panel in a secure location considering both software and hardware vulnerabilities. •...
  • Page 205 6820 / 6820EVS Manual P/N LS10144-001SK-E:C 09/28/2017...
  • Page 206: Limited Warranty

    Products are date stamped at time of manufacture. The sole and exclusive obligation of Honeywell International Inc. is to repair or replace, at its option, free of charge for parts and labor, any part that is defective in materials or workmanship under normal use and service.
  • Page 207: 6820 Basic Operating Instructions

    6820 Basic Operating Instructions These instructions must be framed and displayed next to the 6820 panel in accordance with NFPA 72 fire code for Local Protected Fire Alarm Systems. Operation Keystrokes Silence Alarms and Press SILENCE then rotate the key or enter a code if prompted. Silence LED will light. Troubles Reset alarms Press RESET then rotate the key or enter a code if prompted.
  • Page 209: 6820Evs Basic Operating Instructions

    6820EVS Basic Operating Instructions These instructions must be framed and displayed next to the 6820EVS panel in accordance with NFPA 72 fire code for Local Protected Fire Alarm Systems FS= Fire System EVS = Emergency Voice System Operation Task to Perform Silence Alarms and Press SILENCE then enter a code if prompted.
  • Page 210 P/N: LS10161-001SK-E Rev A ECN 16-.0218 ECN:...
  • Page 211 Integrated Voice Operation Ready to NON-ACTIVE CALL EVS Control Talk LED Button ALL CALL Select EVS Status LED LED’s Message (1-8) Activate Keys Message LEDS Select Keys Table 1: LED Conditions Color States Meaning The corresponding area is active for the currently playing EVS message.
  • Page 212 P/N: LS10161-001SK-E Rev A ECN 16-.0218 ECN:...
  • Page 213 Table 2: EVS Control Request Operation Task Press the EVS Control Key and enter a code if prompted. If EVS Control is available, the EVS Control LED will illuminate. If another LOC has EVS Gain EVS Control at an LOC Control, the display will be similar to the one shown.
  • Page 214 P/N: LS10161-001SK-E Rev A ECN 16-.0218 ECN:...
  • Page 216 Honeywell Silent Knight 12 Clintonville Road Northford, CT 06472-1610 203.484.7161 LS10144-001SK-E | Rev C | 11/17 www.silentknight.com ©May 29, 2018 Honeywell...

This manual is also suitable for:

Silent knight 6820Silent knight 6820evs

Table of Contents