Honeywell Silent Knight IntelliKnight 5820XL Installation And Operation Manual page 139

Addressable fire system
Table of Contents

Advertisement

Or
Press
to skip point name edit.
16. Repeat Steps 1 through 15 for all circuits.
Table 7-6: Menu choices for Internal/External Power Module
Choices
Enter Point or Circuit
Select Type
Select Zone/Group
Edit Name
151209
Function
Type Selections
Selections for
each Type
UNUSED
B NOTIF
A NOTIF
CONSTANT
AUX PWR
RESETTABLE
DOOR
MAN PULL
WATERFLOW
SUPERVSY
TAMPER
FIREDRILL
SILENCE
RESET
B SWITCH
PAS_ACK
ZN_AUX1
ZN_AUX2
SYS_AUX1
SYS_AUX2
MAN REL
ILOCK
A SWITCH
Same as B SWITCH
2-WIRE SMK
B DETECTOR
4-WIRE SMK
2-WIRE SMK
A DETECTOR
4-WIRE SMK
firealarmresources.com
Programming
Comments
Constant auxiliary power.
Resettable auxiliary power.
Door holder auxiliary power.
Refer to comments column of
Table 7-5 for description of these
options.
Latch or Non-latching feature only
appears for waterflow, supervisory,
tamper, zone aux1, zone aux2, system
aux1, and system aux2.
Used for
Used for Class B, 2-wire detectors.
Used for Class B, 4-wire detectors.
Used for Class A, 2-wire detectors.
Used for Class A, 4-wire detectors.
Group or Zone selection will appear
depending on the type selected.
See Section 7.2.1.1.
7-25