8.7.1

Single Interlock Zone Releasing

A single interlock zone utilizes a minimum of two addressable detectors and a designated
manual release switch.
Only addressable detectors can be used. No conventional detectors can be used.
Each Single Interlock Zone input requires at least one manual release switch.

Conditions Required for an Pre-Alert Output Activation

If any single addressable detector is activated, the "Pre-Alert" output will activate. This alerts
the user that the initial stages required for a release condition are present. (Also refer to Table
8-3.)

Conditions required for an General Alarm and Release Output Activation

If two or more addressable detectors, or a manual release switch activate, the "Alarm" and the
"Release" outputs will activate. (Also refer to Table 8-3.)
Inputs
1st Addressable Detector
2nd Addressable Detector
Manual Release Station
151209
Important!
Table 8-3: Single Interlock Zone Operation
firealarmresources.com
Output Results
System Operation
8-15