Addressing Devices; Sd505-Aps, Sd505-Ahs, & Sd505-Ais - Honeywell Silent Knight IntelliKnight 5820XL Installation And Operation Manual

Addressable fire system
Table of Contents

Advertisement

IntelliKnight 5820XL Installation Manual
5.5

Addressing Devices

This section tells how to address detectors and modules.
5.5.1
SD505-APS, SD505-AHS, & SD505-AIS
The SD505-APS photoelectric smoke detector, SD505-AHS heat detector, and SD505-AIS
ionization smoke detector are easily addressed at the FACP. The Installer Code is required to
perform this task.
To address a SD505-APS, SD505-AHS, or SD505-AIS:
1. Connect a detector base temporarily to the programming terminals as shown in
Figure 5-5. (You can use the same base for each detector.)
Figure 5-5 Temporary Connection of Detector Base to Panel for Addressing
2. Enter the Installer code, then press
3. Select
for Point Functions.
2
4. Select
for Set SLC Dev Addr.
3
5. Select "Yes" by pressing the
trouble at this point. You can use the
automatically when the panel reinitializes when you finish programming.)
6. When the wait message clears, the following options display:
for Read Address. Use to read (or check) a single detector's address.
1
for Write Address. Use to program a single detector's address.
2
for Seq. Programming. Use to program more than one detector in sequential order.
3
5-6
.
ENTER
up arrow, then press
key to stop the PZT. The trouble will clear
SILENCE
firealarmresources.com
. (The panel will go into
ENTER
151209