8. Select the characters for the zone name by pressing the
character is shown then press
OR
Enter the Numerical Designator for the character you want, then press
of this manual for a list of available characters and their numeric designators.
9. Repeat step 8 until the name is complete.
10. Press
when the name is complete.
7.4.1.2 Edit Group Properties
The Edit Group Menu allows you to select options for each group for the following items:
•
Latching or non-latching outputs.
•
Silencing operation.
•
Operation with system switches.
Figure 7-8 Group Properties Screen Programming Options
Latching / Non-latching Outputs
Outputs that are programmed as Latching remain active until the system has been manually
reset. Non-latching outputs stop activating automatically when the condition clears.
Silencing Options
The following silencing options are available for each output group.
Option
SILENCE
Silenceable. The output group can be silenced through the
NON-SIL
Not silenceable. The output group cannot be silenced. Activation of the
ignored for this output group.
151209
.
Table 7-2: Silencing Options
Description
firealarmresources.com
Programming
or
arrow until the desired
. See Appendix B
SILENCE
key.
SILENCE
key will be
7-15