4.11 Telephone Connection

Connect the telephone lines as shown in Figure 4-29. The Model 7860 phone cord is available
from Silent Knight for this purpose.
A number of programmable options are available for customizing telephone lines. These
options are described in Section 7.6.

4.12 5211 Ground Start Relay

Note: Do not use ground start in UL installations.
If connecting the control panel to a ground start telephone network, you must use the 5211
ground start relay (order separately).
To install the 5211:
1. Install the 5211 on the ground relay socket as shown in Figure 4-29.
2. Enable ground start through the ground start programming option as described in Section
7.6.2.6
151209
Figure 4-29 Connection of Telephone Lines
firealarmresources.com
Control Panel Installation
5211 Ground
Start Relay Socket
4-29