Output Point Configuration
Conventional notification circuits (circuits 1-6):
Enable circuits used for notification appliances through programming, if
necessary. (JumpStart enables circuits 1-6 as Notification.)
Conventional relay circuits (circuits 7-8):
Select options for relay circuits, if desired. Note: Relay circuits will always
output continuously (constant pattern), even if assigned to an Output Group
that uses a different output pattern.
Auxiliary power circuits (circuits 1-6):
Enable any circuit used for auxiliary power devices through programming.
Select type of power (door holder, constant, or resettable)
Addressable relay modules
Assign addressable relay modules to output groups through programming.
(JumpStart assigns all relay modules to Group 1.)
LED output points (from the 5880 LED I/O module or 5865/66 LED Annunciator)
Assign LED modules to output groups through programming.
All output circuits (1-8):
Disable (set to UNUSED) any unused circuits. If you do not disable unused
output circuits, they will cause a trouble condition (unless an EOL resistor
is used).
Select a name for the point, if desired.
Output Group Configuration
Add the group to the system if it does not already exist.
Assign output points to the group.
Program a name (or description) for the group, if desired.
Select "group properties" (see below).
Latching / non-latching
Silencing option
Select options for activation with system switches.
Map zones to output groups that will activate when zone goes into alarm.
Select a cadence pattern for outputs in the zone.
151209
Task
firealarmresources.com
Before You Begin Installing
See Sec.
(for more info.)
7.4.1
7.4.1
7.5
7.5
7.5
7.5.3
7.5
7.5
7.4.2
7.5
7.4.1.1
7.4.1
7.4.1
7.4.1
7.3.1.3
7.3.1.3