Conventional Input Switch Circuits; Class B Inputs - Honeywell Silent Knight IntelliKnight 5820XL Installation And Operation Manual

Addressable fire system
Table of Contents

Advertisement

4.13.2 Conventional Input Switch Circuits

This section of the manual explains how to install conventional initiating devices for Class A
(Style D) or Class B (Style B) configurations.

4.13.2.1 Class B Inputs

You can connect conventional Class B switches, such as waterflow switches and pull stations,
directly to the Flexput circuits of the control panel.
To install a Class B switch:
1. Wire the Class B switch as shown in Figure 4-32.
2. Configure the circuit through programming (see Section 7.5).
151209
Supervised
Power Limited
UL Listed EOL
Model 7628
4.7 kΩ
Figure 4-32 Class B Input Switches