IntelliKnight 5820XL Installation Manual
4.4

SBUS Wiring

This section contains information on calculating SBUS wire distances and the types of wiring
configurations (Class A and B).
4.4.1

Calculating Wiring distance for SBUS modules

The following instructions will guide you in determining the type of wire and the maximum
wiring distance that can be used with control panel SBUS accessory modules.
To calculate the wire gauge that must be used to connect SBUS modules to the control panel,
it is necessary to calculate the total worst case current draw for all modules on a single 4-
conductor bus. The total worst case current draw is calculated by adding the individual worst
case currents for each module. The individual worst case values are shown in the table below.
Note: Total worst case current draw on a single SBUS cannot exceed 1 amp. If a large number of accessory mod-
ules are required, and the worst case current draw will exceed the 1 amp limit, then the current draw must
be distributed using 5895XL Power Expanders. Each 5895XL Power Expander provides an additional
SBUS, with an additional 1 amp of SBUS current. Wiring distance calculations are done separately for
each 5895XL, and separately for the control panel itself.
5860 Fire Annunciator
5824 Serial/Parallel Printer Interface Module .040 amps
5880 LED I/O Module
5865 LED Fire Annunciator
5895XL Intelligent Power Supply
5496 Intelligent Power Supply
Note: Refer to Table 3-1 for maximum number of each type of device that can be used per system.
After calculating the total worst case current draw, Table 4-1 specifies the maximum distance
the modules can be located from the panel on a single wire run. The table insures 6.0 volts of
line drop maximum. In general, the wire length is limited by resistance, but for heavier wire
gauges, capacitance is the limiting factor.
4-6
Model Number
firealarmresources.com
Worst Case Current Draw
.100 amps
.250 amps
.200 amps
.010 amps
.010 amps
151209