Slc Device Installation; List Of Slc Devices - Honeywell Silent Knight IntelliKnight 5820XL Installation And Operation Manual

Addressable fire system
Table of Contents

Advertisement

Section 5

SLC Device Installation

To avoid the risk of electrical shock and damage to the unit, power should be OFF at the
5.1

List of SLC Devices

The following SLC devices can be used with the control panel. See the appropriate section
number in this manual or the device installation instructions (packaged with the device) for
more information.
Model Number
SD505-APS
Photoelectric smoke detector.
SD505-AIS
Ionization smoke detector
SD505-AHS
Absolute temperature heat detector. Trip point range from 135°F–150°F (0°C–37°C).
SD505-6AB
6" base for use with the SD505-AHS, SD505-AIS, and SD505-APS.
SD505-6IB
6" short circuit isolator base for use with the SD505-AHS, SD505-AIS, and SD505-APS
SD505-6RB
6" relay base for use with the SD505-AHS, SD505-AIS, and SD505-APS
SD505-6SB
6" sounder base for use with the SD505-AHS, SD505-AIS, and
SD505-APS SLC devices
SD505-DUCT
Duct Smoke Detector. Duct Housing including the SD505-APS Analog Photoelectric Smoke
Sensor. Intake tubing for duct available in three lengths:
SD505-T2.5 ( 2.5 foot); SD505-T5 (5 foot); SD505-T10 (10 foot)
SD505-ADH
Duct Detector Housing for use with the SD505-AIS or SD505-APS smoke detectors. Intake
tubing for duct available in three lengths:
STS-2.5: Duct widths 1.0' to 2.5'; STS-5.0: Duct widths 2.5' to 5.0'; STS-10.0: Duct widths
5.0' to 10.0' When ordering SD505-ADH, specify intake tubing size and order the appropriate
smoke detector (if needed).
SD505-ADHR
Duct detector housing with relay (for use with SD505-AIS or SD505-APS smoke detectors)
SD500-PS/-PSDA
Single or dual action addressable pull station
SD500-AIM
Addressable input module (switch input), standard size, dipswitch configurable
SD500-MIM
Mini input monitor module (switch input), small size, dipswitch configurable. Fits in single-
gang box with manual pull station switch.
SD500-ANM
Addressable notification module
SD500ARM
Addressable relay module dipswitch configurable.
SD500-SDM
Addressable smoke detector module. Use to assign an address to a loop of conventional
devices.
SD500-LIM
Line isolator module. Fits in a double gang box.
SD500-LED
Addressable LED driver module. Capable of driving up to 80 LEDs. Up to 40 SD500-LED
Driver Modules can be used per SLC loop.
SD505-DTS
Remote test switch & LED indicator for the SD505-ADHR
151209
Caution!
control panel while installing or servicing.
Model Name/Description
firealarmresources.com
Section No./
Installation
Instructions PN
5.4
5.4
5.4
150955
151175
151192
151191
1700-09882
151040
151126
151177
151071
151071
151109
151091
151193
151125
151232
151126
5-1