Electrical Specifications - Honeywell Silent Knight IntelliKnight 5820XL Installation And Operation Manual

Addressable fire system
Table of Contents

Advertisement

IntelliKnight 5820XL Installation Manual
3.3

Electrical Specifications

Terminal # and Label
1
L
AC input (hot)
2
Earth ground
3
N
AC input (neutral)
4
X
*I/O 6
Flexput™ Circuits
5
O
6
X
*I/O 5
Flexput™ Circuits
7
O
8
X
*I/O 4
Flexput™ Circuits
9
O
10
X
*I/O 3
Flexput™ Circuits
11
O
12
X
*I/O 2
Flexput™ Circuits
13
O
14
X
*I/O 1
Flexput™ Circuits
15
O
16
B
SBUS communication
17
A
SBUS OUT
18
+
SBUS power
19
-
20
B
21
A
SBUS IN
Used for Class A installations
22
+
23
-
24
N.C.
25
C
RELAY 2
General Purpose Relay 2
26
N.O.
27
N.C.
28
C
RELAY 1
General Purpose Relay 1
29
N.O.
30
N.C.
31
C
TROUBLE Trouble Relay
32
N.O.
33
SC-
L1
SLC terminals
34
SC+
SLC OUT
35
SC-
L2
Used for Class A installations
36
SC+
SLC IN
*
Regulated/Special application when used for releasing.
3-2
Description
Voltage
120 VAC, 60 Hz
N/A
120 VAC 60 Hz
24 VDC
24 VDC
24 VDC
24 VDC
24 VDC
24 VDC
5 VDC
24 VDC
24 VDC
24 VDC
24 VDC
32 VDC
firealarmresources.com
Rating
Earth Ground
Current
2.5 A
N/A
2.5 A
3.0 Amp Notification and
Aux power Circuits
100 mA for initiation circuits
3.0 Amp Notification and
Aux power Circuits
100 mA for initiation circuits
3.0 Amp Notification and
Aux power Circuits
100 mA for initiation circuits
3.0 Amp Notification and
Aux power Circuits
100 mA for initiation circuits
3.0 Amp Notification and
Aux power Circuits
100 mA for initiation circuits
3.0 Amp Notification and
Aux power Circuits
100 mA for initiation circuits
100 mA
1.0 A
2.5 A, resistive
2.5 A, resistive
2.5 A, resistive
150 mA
Faults
N/A
N/A
N/A
N/A
N/A
N/A
151209

Advertisement

Table of Contents
loading

Table of Contents